ABB XT2S 160 3 pole Standard MCCB Adjustable Thermal-Magnetic Release In=40A Ii=400A

MPN: 1SDA067554R1

Alt. SKU: XT2S 160 TMA 40-400 3p F F

Special Price £312.53 £260.44 Regular Price £480.80

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067554R1]

The C.BREAKER TMAX XT2S 160 is a fixed three-pole circuit breaker featuring front-access terminals for straightforward installation and maintenance. It incorporates a thermomagnetic release (TMA R 40) providing reliable protection with adjustable current ratings from 200 to 400 A. Designed for robust performance, this breaker ensures precise overload and short-circuit protection in industrial and commercial electrical systems.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with thermomagnetic release TMA R.
  • Rated Voltage: 690 V AC / 500 V DC.
  • Rated Current (I n ): 160 A continuous, with setting range 28...40 A.
  • Short-Circuit Breaking Capacity (I cs / I cu ): Up to 85 kA at 220-240 V AC, reducing to 12 kA at 690 V AC; 50 kA for DC (2 or 3 poles in series).
  • Impulse Withstand Voltage (U imp ): 8 kV.
  • Number of Poles: 3 poles.
  • Terminal Type: Front bolt terminals suitable for busbars 32.5–100 mm²; tightening torque 6 N·m.
  • Electrical Durability: 8,000 operation cycles at 120 cycles/hour.
  • Mechanical Durability: 25,000 operation cycles at 240 cycles/hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the TMAX XT2S 160?
The rated current (I n) is 160 A continuous, with a setting range of 28...40 A.
What is the short-circuit breaking capacity of this circuit breaker?
It has a short-circuit breaking capacity of up to 85 kA at 220-240 V AC, reducing to 12 kA at 690 V AC, and 50 kA for DC (2 or 3 poles in series).
What type of terminals does the TMAX XT2S 160 have?
It features front bolt terminals suitable for busbars of 32.5–100 mm².
What is the tightening torque for the terminals?
The tightening torque for the terminals is 6 N·m.
What is the electrical durability of the TMAX XT2S 160?
The electrical durability is rated for 8,000 operation cycles at 120 cycles/hour.
What is the impulse withstand voltage of this circuit breaker?
The impulse withstand voltage (U imp) is 8 kV.
What standards and approvals does the TMAX XT2S 160 comply with?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA067554R1
Barcode 8015644014506
Manufacturer ABB
Number of Poles 3 Pole
Amperage 40A
Alternative Product SKU XT2S 160 TMA 40-400 3p F F