Do you need some help?

Call us now on: 01706 242050

ABB XT2N 160 4 pole Normal MCCB Electronic trip unit LSI Ii=63A

MPN: 1SDA067104R1

Alt. SKU: XT2N 160 Ekip LSI In=63A 4p F F

Special Price £1,192.32 £993.60 Regular Price £1,834.34

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067104R1]

The TMAX XT2N 160 fixed four-pole circuit breaker features front terminals for straightforward installation and maintenance. It incorporates a solid-state release with EKIP C DIP LSI protection, providing reliable long-time, short-circuit, and earth-fault trip functions. Rated at 63 A, this breaker is designed for precise and consistent performance in AC distribution systems, ensuring compatibility with a range of industrial and commercial applications.

Technical Specification

  • Function: Fixed four-pole moulded case circuit breaker with solid-state release (Ekip C Dip LSI).
  • Rated Current (Iₙ): 63 A.
  • Rated Operational Voltage (Uᵣ): 690 V AC.
  • Number of Poles: 4P.
  • Rated Impulse Withstand Voltage (Uᵢₘₚ): 8 kV.
  • Rated Insulation Voltage (Uᵢ): 1000 V AC.
  • Short-Circuit Breaking Capacity (I cs / I cu): Up to 65 kA at 220-240 V AC; decreasing to 10 kA at 690 V AC.
  • Terminal Connection: Front bolt terminals, suitable for busbar 32.5 to 100 mm².
  • Mechanical Durability: 25,000 operations.
  • Tightening Torque: 6 N·m.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT2N?
The rated current is 63 A.
What is the maximum operational voltage for this circuit breaker?
The maximum rated operational voltage is 690 V AC.
How many poles does the TMAX XT2N circuit breaker have?
This circuit breaker has four poles (4P).
What is the short-circuit breaking capacity at 690 V AC?
The short-circuit breaking capacity decreases to 10 kA at 690 V AC.
What type of terminal connection does this circuit breaker use?
It uses front bolt terminals suitable for busbar sizes from 32.5 to 100 mm².
What is the mechanical durability of the TMAX XT2N?
The mechanical durability is rated for 25,000 operations.
What are the tightening torque specifications for this circuit breaker?
The tightening torque is 6 N·m.
More Information
Manufacturer Part Number 1SDA067104R1
Barcode 8015644010096
Manufacturer ABB
Number of Poles 4 Pole
Amperage 63A
Alternative Product SKU XT2N 160 Ekip LSI In=63A 4p F F
Product Lead Time Please contact us for a delivery time
Write Your Own Review
You're reviewing:ABB XT2N 160 4 pole Normal MCCB Electronic trip unit LSI Ii=63A