Why Choose the Moulded Case Circuit Breaker [1SDA067095R1]

The TMAX XT2N 160A fixed four-pole circuit breaker features front terminals for straightforward installation and maintenance. Equipped with a solid-state release, it offers precise and reliable protection in AC applications. Integrated with EKIP DIP LS/I R technology, this breaker ensures advanced electronic trip functions and enhanced system monitoring, making it suitable for demanding industrial and commercial electrical installations.

Technical Specification

  • Function: Moulded Case Circuit Breaker with solid-state release (Ekip Dip LS/I).
  • Poles: 4-pole fixed configuration with front terminals.
  • Rated Current: 160 A.
  • Rated Operational Voltage: 690 V AC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Breaking Capacity (Ics / Icu): Up to 65 kA at 220-240 V AC, reducing to 10 kA at 690 V AC.
  • Terminal Type and Size: Front bolt terminals, busbar connection 32.5–100 mm², tightening torque 6 N·m.
  • Mechanical Durability: 25,000 cycles.
  • Electrical Durability: 8,000 cycles at 120 cycles/hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the function of the C.BREAKER TMAX XT2N 160?
It is a moulded case circuit breaker with a solid-state release (Ekip Dip LS/I).
What is the rated current and voltage for this circuit breaker?
The rated current is 160 A, and the rated operational voltage is 690 V AC.
What is the short-circuit breaking capacity of the TMAX XT2N 160?
It can handle up to 65 kA at 220-240 V AC, reducing to 10 kA at 690 V AC.
What type of terminals does this circuit breaker have?
It features front bolt terminals with a busbar connection size of 32.5–100 mm².
What is the mechanical durability of the TMAX XT2N 160?
The mechanical durability is rated for 25,000 cycles.
How many electrical cycles can the circuit breaker handle?
It can handle 8,000 electrical cycles at a rate of 120 cycles per hour.
What standards and approvals does this product conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA067095R1
Barcode 8015644010003
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 4 Pole
Amperage 160A
Alternative Product SKU XT2N 160 Ekip Dip LS/I In=160A 4pFF InN=100%