Why Choose the Moulded Case Circuit Breaker [1SDA067093R1]

The TMAX XT2N 160 four-pole fixed circuit breaker features front terminals for straightforward installation and maintenance. It incorporates a solid-state release for precise and reliable protection in AC applications. Designed for use with the EKIP DIP LS/I R electronic trip unit, this breaker is rated at 100 A, ensuring dependable performance in industrial and commercial electrical distribution systems.

Technical Specification

  • Function: Moulded Case Circuit Breaker, fixed four-pole with solid-state Ekip Dip LS/I release.
  • Rated Current (In): 100 A
  • Rated Operational Voltage: 690 V AC
  • Number of Poles: 4P
  • Rated Insulation Voltage (Ui): 1000 V
  • Rated Impulse Withstand Voltage (Uimp): 8 kV
  • Short-Circuit Breaking Capacity (Ics): Up to 65 kA at 220-240 V AC, decreasing to 10 kA at 690 V AC
  • Connecting Capacity: Busbar 32.5 to 100 mm², front terminals with bolts
  • Mechanical Durability: 25,000 cycles
  • Electrical Durability: 8,000 cycles at 120 operations per hour

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT2N?
The rated current (I n) is 100 A.
What is the maximum operational voltage for this circuit breaker?
The rated operational voltage is 690 V AC.
How many poles does the TMAX XT2N have?
This circuit breaker has four poles (4P).
What is the short-circuit breaking capacity of this breaker?
The short-circuit breaking capacity is up to 65 kA at 220-240 V AC, decreasing to 10 kA at 690 V AC.
What is the connecting capacity for the front terminals?
The connecting capacity for the front terminals is 32.5 to 100 mm².
What is the mechanical durability of the TMAX XT2N?
The mechanical durability is rated for 25,000 cycles.
What is the electrical durability of this circuit breaker?
The electrical durability is 8,000 cycles at 120 operations per hour.
More Information
Manufacturer Part Number 1SDA067093R1
Barcode 8015644009984
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 4 Pole
Amperage 100A
Alternative Product SKU XT2N 160 Ekip Dip LS/I In=100A 4p F F