Why Choose the Moulded Case Circuit Breaker [1SDA067072R1]

The TMAX XT2N 160 fixed three-pole circuit breaker features front terminals for straightforward installation and maintenance. It incorporates a solid-state release with LSIG protection, providing reliable long-time, short-circuit, and ground fault tripping. Designed for AC applications, this breaker includes an EKIP C DIP electronic trip unit adjustable to 10 A, ensuring precise and adaptable overload protection. Its robust construction and advanced trip technology make it suitable for demanding industrial and commercial electrical systems.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with solid-state release Ekip C Dip LSIG.
  • Rated Current (In): 10 A.
  • Rated Operational Voltage (Ur): 690 V AC.
  • Number of Poles: 3 poles (3P).
  • Rated Insulation Voltage (Ui): 1000 V AC.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Breaking Capacity: Up to 65 kA at 220-240 V AC; reducing to 10 kA at 690 V AC.
  • Terminal Type: Front terminals with bolt connection.
  • Connecting Capacity: Busbar 32.5 to 100 mm².
  • Mechanical Durability: 25,000 operating cycles.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT2N?
The rated current (I n) of the C.BREAKER TMAX XT2N is 10 A.
What is the maximum operational voltage for this circuit breaker?
The maximum rated operational voltage (U r) is 690 V AC.
How many poles does the TMAX XT2N circuit breaker have?
The TMAX XT2N circuit breaker has 3 poles (3P).
What is the short-circuit breaking capacity of this breaker?
The short-circuit breaking capacity is up to 65 kA at 220-240 V AC and reduces to 10 kA at 690 V AC.
What type of terminals does the TMAX XT2N feature?
The TMAX XT2N features front terminals with bolt connection.
What is the connecting capacity for busbars?
The connecting capacity for busbars is 32.5 to 100 mm².
What is the mechanical durability of the circuit breaker?
The mechanical durability is rated for 25,000 operating cycles.
More Information
Manufacturer Part Number 1SDA067072R1
Barcode 8015644009762
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 10A
Alternative Product SKU XT2N 160 Ekip LSIG In=10A 3p F F