ABB XT2N 160 3 pole Normal MCCB Adjustable Thermal-Magnetic Release In=100A Ii=1000A

MPN: 1SDA067018R1

Alt. SKU: XT2N 160 TMA 100-1000 3p F F

Special Price £245.33 £204.44 Regular Price £377.44

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067018R1]

The TMAX XT2N 160 fixed three-pole circuit breaker features front-access terminals and a thermomagnetic release (TMA R 100) designed for reliable protection. It offers adjustable current settings ranging from 500 A to 1000 A (I3), ensuring precise coordination in industrial and commercial electrical installations. Engineered for durability and compatibility with standard switchgear, this breaker provides dependable overload and short-circuit protection in demanding environments.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with thermomagnetic release (TMA R).
  • Rated Current: 160 A (uninterrupted), Setting range 70–100 A.
  • Rated Operational Voltage: 690 V AC / 500 V DC.
  • Short-Circuit Breaking Capacity (Ics): Up to 65 kA (220–240 V AC), 36 kA (380–440 V AC), 10 kA (690 V AC), and 36 kA for DC configurations.
  • Insulation Voltage (Ui): 1000 V.
  • Impulse Withstand Voltage (Uimp): 8 kV.
  • Number of Poles: 3 poles (3P).
  • Terminal Type and Size: Front bolt terminals, busbar connection 32.5 to 100 mm², tightening torque 6 N·m.
  • Mechanical Durability: 25,000 cycles.
  • Electrical Durability: 8,000 cycles at 120 cycles/hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT2N 160?
The rated current is 160 A (uninterrupted), with a setting range of 70–100 A.
What is the short-circuit breaking capacity of this circuit breaker?
It has a short-circuit breaking capacity of up to 65 kA at 220–240 V AC, 36 kA at 380–440 V AC, 10 kA at 690 V AC, and 36 kA for DC configurations.
What type of terminals does the TMAX XT2N 160 have?
The circuit breaker features front bolt terminals with a busbar connection size of 32.5 to 100 mm².
What is the insulation voltage for this product?
The insulation voltage (Ui) is 1000 V.
How many poles does the C.BREAKER TMAX XT2N 160 have?
This circuit breaker is a fixed three-pole (3P) device.
What is the mechanical durability of the circuit breaker?
The mechanical durability is rated for 25,000 cycles.
What standards and approvals does this product conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA067018R1
Barcode 8015644694937
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 100A
Alternative Product SKU XT2N 160 TMA 100-1000 3p F F
Write Your Own Review