Why Choose the Moulded Case Circuit Breaker [1SDA067008R1]

The TMAX XT2N 160 fixed three-pole circuit breaker features front-access terminals and a thermomagnetic release (TMD R) adjustable from 10 to 100 A. Designed for reliable protection and precise current interruption, it is suitable for industrial and commercial electrical installations requiring robust overload and short-circuit safeguarding. Its fixed configuration ensures secure mounting, while front terminals facilitate straightforward wiring and maintenance.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with thermomagnetic release (TMD).
  • Rated Operational Voltage: 690 V AC / 500 V DC.
  • Rated Current: 10 A (setting range 7–10 A).
  • Contact Configuration: 3 poles.
  • Rated Insulation Voltage: 1000 V.
  • Impulse Withstand Voltage: 8 kV.
  • Terminal Type: Front terminals with bolt connections, suitable for busbars 32.5–100 mm².
  • Mechanical Durability: 25,000 cycles at 240 cycles per hour.
  • Electrical Durability: 8,000 cycles at 120 cycles per hour.
  • Short-Circuit Breaking Capacity (Ics): Up to 65 kA AC depending on voltage; 36 kA DC for 2 or 3 poles in series.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated operational voltage of the TMAX XT2N 160?
The rated operational voltage is 690 V AC and 500 V DC.
What is the setting range for the rated current?
The rated current has a setting range of 7–10 A.
What type of terminals does this circuit breaker have?
It features front terminals with bolt connections, suitable for busbars of 32.5–100 mm².
What is the short-circuit breaking capacity of the TMAX XT2N 160?
The short-circuit breaking capacity is up to 65 kA AC and 36 kA DC for 2 or 3 poles in series, depending on voltage.
How many mechanical cycles can this circuit breaker endure?
The mechanical durability is rated for 25,000 cycles at 240 cycles per hour.
What is the electrical durability of the TMAX XT2N 160?
The electrical durability is rated for 8,000 cycles at 120 cycles per hour.
What standards and approvals does this product conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA067008R1
Barcode 8015644694906
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 10A
Alternative Product SKU XT2N 160 TMD 10-100 3p F F