ABB XT2N 160 3 pole Normal MCCB Fixed Thermal/Adjustable Magnetic Release In=3.2A Ii=32A

MPN: 1SDA067003R1

Alt. SKU: XT2N 160 TMD 3,2-32 3p F F

Special Price £248.48 £207.07 Regular Price £382.28

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067003R1]

The C.BREAKER TMAX XT2N 160 is a fixed three-pole circuit breaker featuring front-access terminals for straightforward installation and maintenance. It incorporates a thermomagnetic release (TMD R) adjustable between 3.2 and 32 A, providing reliable protection against overloads and short circuits. Designed for compatibility with a wide range of electrical distribution systems, this breaker ensures precise and durable performance in industrial and commercial applications.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with thermomagnetic release TMD R.
  • Rated Operational Voltage: 690 V AC / 500 V DC.
  • Rated Current: 3.2 A (setting range 2.24 to 3.2 A).
  • Number of Poles: 3 poles (3P).
  • Rated Insulation Voltage: 1000 V.
  • Rated Impulse Withstand Voltage: 8 kV.
  • Short-Circuit Breaking Capacity (Icu / Ics): Up to 65 kA (220–240 V AC), 36 kA (380–440 V AC), 10 kA (690 V AC), and 36 kA at 250 V DC (2 poles in series) / 500 V DC (3 poles in series).
  • Terminal Type: Front bolt terminals suitable for busbar connection 32.5 to 100 mm².
  • Electrical Durability: 8,000 operating cycles at 120 cycles/hour.
  • Mechanical Durability: 25,000 operating cycles at 240 cycles/hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated operational voltage of the C.BREAKER TMAX XT2N 160?
The rated operational voltage is 690 V AC / 500 V DC.
What is the setting range for the rated current?
The rated current has a setting range of 2.24 to 3.2 A.
How many poles does this circuit breaker have?
This circuit breaker has 3 poles (3P).
What is the short-circuit breaking capacity of the breaker?
The short-circuit breaking capacity is up to 65 kA at 220–240 V AC, 36 kA at 380–440 V AC, 10 kA at 690 V AC, and 36 kA at 250 V DC (2 poles in series) / 500 V DC (3 poles in series).
What type of terminals does the circuit breaker have?
The circuit breaker features front bolt terminals suitable for busbar connection of 32.5 to 100 mm².
What is the electrical durability of the C.BREAKER TMAX XT2N 160?
The electrical durability is rated for 8,000 operating cycles at 120 cycles/hour.
What is the mechanical durability of this circuit breaker?
The mechanical durability is rated for 25,000 operating cycles at 240 cycles/hour.
More Information
Manufacturer Part Number 1SDA067003R1
Barcode 8015644009076
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 3.2A
Alternative Product SKU XT2N 160 TMD 3,2-32 3p F F
Write Your Own Review
You're reviewing:ABB XT2N 160 3 pole Normal MCCB Fixed Thermal/Adjustable Magnetic Release In=3.2A Ii=32A