Why Choose the Moulded Case Circuit Breaker [1SDA064887R1]

The TMAX T7S 1200 four-pole circuit breaker features a fixed design with front terminals for straightforward installation and maintenance. It incorporates a stored energy operating mechanism combined with a solid-state release, ensuring precise and reliable tripping performance. Certified to UL and CSA standards, this breaker is suitable for demanding AC applications and offers robust protection with the PR232/P-LSI R 1200 release unit.

Technical Specification

  • Function: Moulded Case Circuit Breaker, 4 poles (4P) with stored energy operating mechanism.
  • Rated Current (Iₙ): 1200 A.
  • Rated Operational Voltage: 630 V AC.
  • Impulse Withstand Voltage (Uimp): 8 kV.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Interrupting Rating (UL489): 65 kA @ 240 V AC, 50 kA @ 480 V AC, 25 kA @ 600 V AC.
  • Terminal Type: Fixed, front connection.
  • Mechanical Durability: 10,000 cycles at 60 cycles per hour.
  • Power Loss: 47 W per pole at rated conditions.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T7S?
The rated current is 1200 A.
What is the rated operational voltage for this circuit breaker?
The rated operational voltage is 630 V AC.
What is the interrupting rating for the C.BREAKER TMAX T7S?
The interrupting ratings are 65 kA @ 240 V AC, 50 kA @ 480 V AC, and 25 kA @ 600 V AC.
How many poles does this circuit breaker have?
This circuit breaker has 4 poles (4P).
What type of terminals does the C.BREAKER TMAX T7S feature?
It features fixed, front connection terminals.
What is the mechanical durability of the circuit breaker?
The mechanical durability is 10,000 cycles at 60 cycles per hour.
What should I refer to for standards and approvals?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA064887R1
Barcode 8015644677862
Manufacturer ABB
Number of Poles 4 Pole
Amperage 1200A
Alternative Product SKU T7S 1200 UL PR232/P LSI In1200A 4p FF M
Write Your Own Review
You're reviewing:1sda064887r1 t7s 1200 ul pr232/p lsi in=1200a 4 pole abb mccb