Do you need some help?

Call us now on: 01706 242050

1sda064882r1 t7s 1200 ul pr331/p lsig in=1200a 3 pole abb mccb

MPN: 1SDA064882R1

Alt. SKU: T7S 1200 UL PR331/P LSIG In1200A 3p FF M

Contact us for pricing and availability.
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA064882R1]

The TMAX T7S 1200 three-pole fixed circuit breaker features front terminals for straightforward installation and a stored energy operating mechanism for reliable switching performance. It incorporates a solid-state release with AC protection (PR331/P-LSIG) rated at 1200A, ensuring precise and consistent trip characteristics. Certified to UL and CSA standards, this breaker is designed for robust operation in demanding industrial and commercial electrical distribution systems.

Technical Specification

  • Function: Moulded Case Circuit Breaker, three-pole fixed with front terminals.
  • Rated Current: 1200 A.
  • Rated Operational Voltage: 630 V AC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Interrupting Capacity (UL489): 65 kA at 240 V AC, 50 kA at 480 V AC, 25 kA at 600 V AC.
  • Release Type: PR331/P LSIG solid-state release.
  • Terminal Type: Fixed, front connection.
  • Mechanical Durability: 10,000 cycles at 60 cycles per hour.
  • Power Loss per Pole: 47 W at rated conditions.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T7S?
The rated current is 1200 A.
What is the rated operational voltage for this circuit breaker?
The rated operational voltage is 630 V AC.
What type of release does the TMAX T7S use?
It uses a PR331/P LSIG solid-state release.
What is the interrupting capacity at 240 V AC?
The interrupting capacity is 65 kA at 240 V AC.
How is the circuit breaker mounted?
It is a three-pole fixed circuit breaker with front terminals.
What is the mechanical durability of the TMAX T7S?
The mechanical durability is 10,000 cycles at 60 cycles per hour.
What are the power loss specifications per pole?
The power loss per pole is 47 W at rated conditions.
More Information
Manufacturer Part Number 1SDA064882R1
Barcode 8015644677817
Manufacturer ABB
Number of Poles 3 Pole
Amperage 1200A
Alternative Product SKU T7S 1200 UL PR331/P LSIG In1200A 3p FF M