Why Choose the Moulded Case Circuit Breaker [1SDA064881R1]

The TMAX T7S 1200 three-pole circuit breaker features a fixed design with front terminals for straightforward installation and maintenance. It incorporates a stored energy operating mechanism combined with a solid-state release, ensuring precise and reliable tripping performance. Certified to UL and CSA standards, this breaker is suitable for demanding AC applications requiring robust protection and compatibility with PR232/P-LSI R 1200 release units.

Technical Specification

  • Function: Moulded Case Circuit Breaker, Three-Pole Fixed with Front Terminals.
  • Rated Current (In): 1200 A.
  • Rated Operational Voltage: 630 V AC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Interrupting Capacity (UL489): 65 kA at 240 V AC, 50 kA at 480 V AC, 25 kA at 600 V AC.
  • Release Type: PR232/P-LSI Solid-State Release.
  • Mechanical Durability: 10,000 operating cycles at 60 cycles per hour.
  • Terminal Connection: Fixed, Front.
  • Test Voltage (Max Utest): 3500 V.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the TMAX T7S circuit breaker?
The rated current of the TMAX T7S circuit breaker is 1200 A.
What is the interrupting capacity of this circuit breaker?
The interrupting capacity is 65 kA at 240 V AC, 50 kA at 480 V AC, and 25 kA at 600 V AC.
What type of release does the TMAX T7S use?
The TMAX T7S uses a PR232/P-LSI solid-state release.
What is the maximum rated operational voltage for this circuit breaker?
The rated operational voltage is 630 V AC.
How is the TMAX T7S circuit breaker mounted?
The circuit breaker is a three-pole fixed type with front terminals.
What is the mechanical durability of the TMAX T7S?
The mechanical durability is 10,000 operating cycles at 60 cycles per hour.
What are the insulation and impulse withstand voltage ratings?
The rated insulation voltage is 1000 V, and the rated impulse withstand voltage is 8 kV.