Why Choose the Moulded Case Circuit Breaker [1SDA064875R1]

The TMAX T7S 1200 four-pole fixed circuit breaker features front terminals and a lever operating mechanism for straightforward installation and operation. It incorporates a solid-state release with PR232/P-LSI technology, providing precise and reliable protection in AC applications. Certified to UL and CSA standards, this breaker is designed for robust performance and compatibility in demanding electrical systems.

Technical Specification

  • Function: Fixed 4-pole moulded case circuit breaker with lever operating mechanism and solid-state PR232/P-LSI release.
  • Rated Current (In): 1200 A.
  • Rated Operational Voltage: 630 V AC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Interrupting Rating (UL489): 65 kA at 240 V AC, 50 kA at 480 V AC, 25 kA at 600 V AC.
  • Terminal Type: Fixed front terminals.
  • Mechanical Durability: 10,000 cycles at 60 cycles per hour.
  • Power Loss per Pole: 47 W at rated operating conditions.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T7S?
The rated current is 1200 A.
What is the maximum operational voltage for this circuit breaker?
The rated operational voltage is 630 V AC.
How many poles does the C.BREAKER TMAX T7S have?
It is a fixed 4-pole moulded case circuit breaker.
What type of release mechanism does this breaker use?
It uses a solid-state PR232/P-LSI release mechanism.
What is the interrupting rating for the circuit breaker?
The interrupting rating is 65 kA at 240 V AC, 50 kA at 480 V AC, and 25 kA at 600 V AC.
What is the mechanical durability of the C.BREAKER TMAX T7S?
The mechanical durability is 10,000 cycles at 60 cycles per hour.
What is the power loss per pole at rated operating conditions?
The power loss per pole is 47 W.
More Information
Manufacturer Part Number 1SDA064875R1
Barcode 8015644677749
Manufacturer ABB
Number of Poles 4 Pole
Amperage 1200A
Alternative Product SKU T7S 1200 UL PR232/P LSI In1200A 4p FF
Product Lead Time Please contact us for a delivery time
Write Your Own Review