Why Choose the Moulded Case Circuit Breaker [1SDA064783R1]

The TMAX T7S 1000 four-pole circuit breaker features a fixed configuration with front terminals for straightforward installation and maintenance. It incorporates a stored energy operating mechanism combined with a solid-state release, ensuring reliable and precise tripping performance. Certified to UL and CSA standards, this breaker is designed for demanding AC applications, providing robust protection and compatibility within industrial and commercial electrical systems.

Technical Specification

  • Function: Four-pole moulded case circuit breaker with stored energy operating mechanism and solid-state PR232/P-LSI release.
  • Rated Current: 1000 A.
  • Operational Voltage: 600 V AC.
  • Impulse Withstand Voltage: 8 kV.
  • Insulation Voltage: 1000 V.
  • Short-Circuit Interrupting Capacity (UL489): 65 kA at 240 V AC, 50 kA at 480 V AC, 25 kA at 600 V AC.
  • Terminal Type: Fixed front terminals.
  • Mechanical Durability: 10,000 operating cycles at 60 cycles per hour.
  • Power Loss per Pole: 30 W.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T7S?
The rated current is 1000 A.
What is the operational voltage for this circuit breaker?
The operational voltage is 600 V AC.
What is the short-circuit interrupting capacity?
The interrupting capacity is 65 kA at 240 V AC, 50 kA at 480 V AC, and 25 kA at 600 V AC.
How many operating cycles can this breaker endure?
The mechanical durability is rated for 10,000 operating cycles at 60 cycles per hour.
What type of terminals does the C.BREAKER TMAX T7S have?
It features fixed front terminals.
What is the insulation voltage of this circuit breaker?
The insulation voltage is 1000 V.
What should I refer to for standards and approvals?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA064783R1
Barcode 8015644676780
Manufacturer ABB
Number of Poles 4 Pole
Amperage 1000A
Alternative Product SKU T7S 1000 UL PR232/P LSI In1000A 4p FF M
Product Lead Time Please contact us for a delivery time
Write Your Own Review
You're reviewing:1sda064783r1 t7s 1000 ul pr232/p lsi in=1000a 4 pole abb mccb