Why Choose the Moulded Case Circuit Breaker [1SDA064772R1]

The TMAX T7S 1000 four-pole circuit breaker features a fixed design with front terminals for straightforward installation and maintenance. Equipped with a lever operating mechanism and a solid-state release, it ensures precise and reliable protection in AC applications. Certified to UL and CSA standards, this model (PR331/P-LSIG R 1000) is suitable for demanding industrial and commercial environments requiring robust overload and short-circuit protection.

Technical Specification

  • Function: Four-pole moulded case circuit breaker with solid-state release.
  • Rated Current: 1000 A.
  • Operational Voltage: 600 V AC.
  • Impulse Withstand Voltage: 8 kV.
  • Insulation Voltage: 1000 V.
  • Interrupting Rating (UL489): 65 kA at 240 V AC, 50 kA at 480 V AC, 25 kA at 600 V AC.
  • Terminal Type: Fixed front terminals.
  • Mechanical Durability: 10,000 operating cycles at 60 cycles per hour.
  • Power Loss: 30 W per pole at rated conditions.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T7S?
The rated current is 1000 A.
What is the operational voltage for this circuit breaker?
The operational voltage is 600 V AC.
What is the interrupting rating for the TMAX T7S at 240 V AC?
The interrupting rating is 65 kA at 240 V AC.
How many operating cycles can the circuit breaker endure?
The mechanical durability is rated for 10,000 operating cycles at 60 cycles per hour.
What type of terminals does the TMAX T7S have?
The circuit breaker features fixed front terminals.
What is the power loss per pole at rated conditions?
The power loss is 30 W per pole at rated conditions.
What standards and approvals does this product conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA064772R1
Barcode 8015644676674
Manufacturer ABB
Number of Poles 4 Pole
Amperage 1000A