Do you need some help?

Call us now on: 01706 242050

1sda062892r1 t7s 1250 pr331/p lsig in=1250a 4 pole abb mccb

MPN: 1SDA062892R1

Alt. SKU: T7S 1250 PR331/P LSIG In=1250A 4p F F M

Special Price £6,950.32 £5,791.93 Regular Price £10,692.79

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA062892R1]

The TMAX T7S 1250 fixed four-pole circuit breaker features front terminals for straightforward installation and maintenance. It incorporates a stored energy operating mechanism for reliable switching performance and a solid-state release unit, providing precise protection with adjustable long-time, short-time, and instantaneous trip settings (LSIG). Designed for AC applications, this breaker ensures robust fault interruption and compatibility with PR331/P trip units, making it suitable for demanding industrial and commercial electrical distribution systems.

Technical Specification

  • Function: Moulded case circuit breaker, fixed four-pole with front terminals.
  • Rated Current (Iₙ): 1250 A.
  • Rated Operational Voltage: 690 V AC.
  • Rated Insulation Voltage (Uᵢ): 1000 V.
  • Rated Impulse Withstand Voltage (Uᵢₘₚ): 8 kV.
  • Short-Circuit Breaking Capacity (I????ₛ): Up to 85 kA at 220-230 V AC, reducing to 30 kA at 690 V AC.
  • Terminal Type: Fixed front terminals.
  • Mechanical Durability: 10,000 cycles at 60 cycles/hour.
  • Electrical Durability: 2,000 cycles at 60 cycles/hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T7S?
The rated current (Iₙ) is 1250 A.
What is the maximum operational voltage for this circuit breaker?
The rated operational voltage is 690 V AC.
What is the short-circuit breaking capacity of the TMAX T7S?
The short-circuit breaking capacity is up to 85 kA at 220-230 V AC, reducing to 30 kA at 690 V AC.
How many mechanical cycles can the TMAX T7S endure?
The mechanical durability is rated for 10,000 cycles at 60 cycles/hour.
What type of terminals does the TMAX T7S have?
The circuit breaker features fixed front terminals.
What is the rated insulation voltage for this product?
The rated insulation voltage (Uᵢ) is 1000 V.
What standards and approvals does the TMAX T7S comply with?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA062892R1
Barcode 8015644654412
Manufacturer ABB
Number of Poles 4 Pole
Amperage 1250A
Alternative Product SKU T7S 1250 PR331/P LSIG In=1250A 4p F F M
Write Your Own Review