The TMAX T7H 1000 fixed three-pole circuit breaker features front terminals for straightforward installation and maintenance. It incorporates a stored energy operating mechanism combined with a solid-state release, ensuring precise and reliable tripping performance. Designed for use in AC applications, this breaker model PR231/P-I R 1000 delivers consistent protection and compatibility with industrial electrical systems.
Technical Specification
- Function: Moulded Case Circuit Breaker, three-pole fixed type.
- Rated Current: 1000 A.
- Rated Operational Voltage: 690 V AC.
- Rated Impulse Withstand Voltage: 8 kV.
- Rated Insulation Voltage: 1000 V.
- Short-Circuit Breaking Capacity (Ics): Up to 100 kA at 220-230 V AC, decreasing to 31.5 kA at 690 V AC.
- Terminal Type: Front fixed terminals.
- Mechanical Durability: 10,000 operating cycles at 60 cycles/hour.
- Electrical Durability: 2,000 operating cycles at 60 cycles/hour.
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What is the rated current of the C.BREAKER TMAX T7H?
What is the maximum operational voltage for this circuit breaker?
What is the short-circuit breaking capacity at 690 V AC?
How many operating cycles can the circuit breaker endure mechanically?
What type of terminals does the C.BREAKER TMAX T7H have?
What is the rated insulation voltage for this product?
What standards and approvals does this product conform to?
| Manufacturer Part Number | 1SDA062785R1 |
|---|---|
| Barcode | 8015644653347 |
| Manufacturer | ABB |
| Number of Poles | 3 Pole |
| Amperage | 1000A |