Why Choose the Moulded Case Circuit Breaker [1SDA061989R1]

The TMAX T7S 800 fixed four-pole circuit breaker features front terminals for straightforward installation and maintenance. It incorporates a stored energy operating mechanism combined with a solid-state release, ensuring precise and reliable tripping performance. Designed for use with AC PR231/P-LS/I R 800 protection modules, this breaker delivers consistent operation in demanding electrical distribution applications.

Technical Specification

  • Function: Fixed four-pole moulded case circuit breaker with stored energy operating mechanism and solid-state release.
  • Rated Current (Iₙ): 800 A.
  • Rated Operational Voltage: 690 V AC.
  • Number of Poles: 4P.
  • Rated Insulation Voltage (Uᵢ): 1000 V.
  • Rated Impulse Withstand Voltage (Uᵢₘₚ): 8 kV.
  • Short-circuit Breaking Capacity (Iₙ): Up to 85 kA at 220-230 V AC, reducing to 30 kA at 690 V AC.
  • Mechanical Durability: 10,000 cycles at 60 cycles per hour.
  • Electrical Durability: 2,000 cycles at 60 cycles per hour.
  • Terminal Type: Front fixed terminals.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T7S?
The rated current is 800 A.
What is the maximum short-circuit breaking capacity?
The maximum short-circuit breaking capacity is up to 85 kA at 220-230 V AC, reducing to 30 kA at 690 V AC.
How many poles does this circuit breaker have?
This circuit breaker has four poles (4P).
What is the rated operational voltage for the TMAX T7S?
The rated operational voltage is 690 V AC.
What type of terminals does the TMAX T7S have?
The TMAX T7S features front fixed terminals.
What is the mechanical durability of this circuit breaker?
The mechanical durability is rated for 10,000 cycles at 60 cycles per hour.
Are there any specific standards or approvals for this product?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA061989R1
Barcode 8015644645359
Manufacturer ABB
Number of Poles 4 Pole
Amperage 800A
Alternative Product SKU T7S 800 PR231/P LS/I In=800A 4p F F M