Why Choose the Moulded Case Circuit Breaker [1SDA061839R1]

The TMAX T5S 600 three-pole circuit breaker features a fixed configuration with front terminals for straightforward installation and maintenance. It incorporates a solid-state release mechanism, ensuring precise and reliable protection in AC applications. Certified to UL and CSA standards, this model PR221DS-LS/I R 600 offers robust performance and compatibility for industrial and commercial electrical systems.

Technical Specification

  • Function: Moulded Case Circuit Breaker, fixed three-pole with front terminals.
  • Rated Current (In): 600 A.
  • Rated Operational Voltage: 600 V AC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Interrupting Rating (UL489): 100 kA @ 240 V AC, 35 kA @ 480 V AC, 25 kA @ 600 V AC.
  • Release Type: Solid-state (PR221DS-LS/I, EL type).
  • Mechanical Durability: 20,000 cycles, 120 cycles per hour.
  • Terminal Connection: Fixed front terminals.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T5S?
The rated current (I n) of the C.BREAKER TMAX T5S is 600 A.
What is the rated operational voltage for this circuit breaker?
The rated operational voltage is 600 V AC.
What type of release does the C.BREAKER TMAX T5S use?
This circuit breaker uses a solid-state release type (PR221DS-LS/I, EL type).
What is the interrupting rating for the C.BREAKER TMAX T5S?
The interrupting ratings are 100 kA @ 240 V AC, 35 kA @ 480 V AC, and 25 kA @ 600 V AC.
What is the mechanical durability of this circuit breaker?
The mechanical durability is rated for 20,000 cycles at 120 cycles per hour.
How are the terminals configured on the C.BREAKER TMAX T5S?
The circuit breaker features fixed front terminals.
What standards and approvals does the C.BREAKER TMAX T5S conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA061839R1
Barcode 8015644643645
Manufacturer ABB
Number of Poles 3 Pole
Amperage 600A
Alternative Product SKU T5S 600 UL/CSA PR221DS-LS/I 600 3p F F
Write Your Own Review
You're reviewing:1sda061839r1 t5s 600ul csa pr221ds-ls/i 600 3 pole abb mccb