Do you need some help?

Call us now on: 01706 242050

1sda061695r1 t6h 800 ul/csa pr222ds/p-lsi 800 3 pole abb mccb

MPN: 1SDA061695R1

Alt. SKU: T6H 800 UL/CSA PR222DS/P-LSI 800 3p F F

Contact us for pricing and availability.
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA061695R1]

The TMAX T6H 800A fixed three-pole circuit breaker features front terminals for straightforward installation and a solid-state release for precise protection. Certified to UL and CSA standards, this model PR222DS/P-LSI R 800 ensures reliable performance in demanding AC applications, offering enhanced safety and compatibility within industrial and commercial electrical systems.

Technical Specification

  • Function: Moulded Case Circuit Breaker, fixed three-pole with front terminals.
  • Rated Current (In): 800 A.
  • Rated Operational Voltage: 600 V AC.
  • Number of Poles: 3P.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Interrupting Rating (UL489): 200 kA at 240 V AC, 65 kA at 480 V AC, 35 kA at 600 V AC.
  • Terminal Type: Fixed, front connection.
  • Mechanical Durability: 20,000 cycles at 120 cycles per hour.
  • Release Type: Solid-state PR222DS/P-LSI release.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T6H 800?
The rated current is 800 A.
What is the maximum operational voltage for this circuit breaker?
The maximum rated operational voltage is 600 V AC.
How many poles does the TMAX T6H 800 circuit breaker have?
It has three poles (3P).
What type of release does this circuit breaker use?
It uses a solid-state PR222DS/P-LSI release.
What is the interrupting rating of the circuit breaker at 480 V AC?
The interrupting rating is 65 kA at 480 V AC.
What is the mechanical durability of the TMAX T6H 800?
The mechanical durability is 20,000 cycles at 120 cycles per hour.
What standards and approvals does this product conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA061695R1
Barcode 8015644642341
Manufacturer ABB
Number of Poles 3 Pole
Amperage 800A
Alternative Product SKU T6H 800 UL/CSA PR222DS/P-LSI 800 3p F F
Write Your Own Review