Why Choose the Moulded Case Circuit Breaker [1SDA061692R1]

The TMAX T6S 800A fixed three-pole circuit breaker features front terminals for straightforward installation and maintenance. Equipped with a solid-state release, it ensures precise and reliable protection in AC applications. Certified to UL and CSA standards, this model PR222DS/P-LSI R 800 offers robust performance and compatibility for industrial and commercial electrical systems.

Technical Specification

  • Function: Moulded Case Circuit Breaker, 3-Pole fixed with front terminals.
  • Rated Current (Iₙ): 800 A.
  • Rated Operational Voltage: 600 V AC.
  • Rated Insulation Voltage (Uᵢ): 1000 V.
  • Rated Impulse Withstand Voltage (Uᵢₘₚ): 8 kV.
  • Interrupting Rating (UL489): 100 kA at 240 V AC, 50 kA at 480 V AC, 25 kA at 600 V AC.
  • Release Type: PR222DS/P-LSI solid-state release.
  • Mechanical Durability: 20,000 cycles at 120 cycles per hour.
  • Terminal Type: Fixed front terminals.
  • Power Loss per Pole: 32 W at rated operating conditions.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T6S 800?
The rated current is 800 A.
What is the maximum operational voltage for this circuit breaker?
The maximum rated operational voltage is 600 V AC.
What type of release does the TMAX T6S 800 use?
It uses a PR222DS/P-LSI solid-state release.
What is the interrupting rating at 240 V AC?
The interrupting rating is 100 kA at 240 V AC.
How many mechanical cycles can this circuit breaker endure?
It has a mechanical durability of 20,000 cycles at 120 cycles per hour.
What type of terminals does the TMAX T6S 800 have?
It features fixed front terminals.
What is the power loss per pole at rated operating conditions?
The power loss per pole is 32 W.