Why Choose the Moulded Case Circuit Breaker [1SDA061662R1]

The TMAX T6S 800 UL/CSA fixed three-pole circuit breaker features front terminals for straightforward installation and maintenance. It incorporates a thermomagnetic release (TMA R 800) providing reliable protection with adjustable trip settings ranging from 4000 to 8000 A. Designed to meet UL and CSA standards, this breaker ensures compatibility and dependable performance in industrial and commercial electrical systems.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with thermomagnetic release (TMA).
  • Rated Current (In): 800 A.
  • Rated Operational Voltage: 600 V AC / 600 V DC.
  • Number of Poles: 3 poles.
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu): 100 kA at 240 V AC, 50 kA at 480 V AC, 25 kA at 600 V AC, 35 kA at 500 V DC (2 poles in series), 20 kA at 600 V DC (3 poles in series).
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Terminal Connection Type: Fixed front terminals.
  • Mechanical Durability: 20,000 mechanical cycles at 120 cycles per hour.
  • Power Loss per Pole: 31 W at rated operating conditions.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the TMAX T6S 800 circuit breaker?
The rated current is 800 A.
What is the rated operational voltage for this circuit breaker?
The rated operational voltage is 600 V AC / 600 V DC.
How many poles does the TMAX T6S 800 have?
This circuit breaker has 3 poles.
What is the rated ultimate short-circuit breaking capacity?
The breaking capacity is 100 kA at 240 V AC, 50 kA at 480 V AC, 25 kA at 600 V AC, 35 kA at 500 V DC (2 poles in series), and 20 kA at 600 V DC (3 poles in series).
What type of terminal connection does the TMAX T6S 800 use?
It uses fixed front terminals.
What is the mechanical durability of this circuit breaker?
The mechanical durability is 20,000 cycles at 120 cycles per hour.
What is the rated insulation voltage for the TMAX T6S 800?
The rated insulation voltage is 1000 V.