Do you need some help?

Call us now on: 01706 242050

1sda060452r1 t5n 400ul csapr222ds/p-lsi in=400 4 pole abb mccb

MPN: 1SDA060452R1

Alt. SKU: T5N 400 UL/CSA PR222DS/P-LSI 400 4p F F

Contact us for pricing and availability.
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA060452R1]

The TMAX T5N 400A fixed four-pole circuit breaker features front terminals for straightforward installation and maintenance. It incorporates a solid-state release mechanism, providing precise and reliable protection in AC applications. Certified to UL and CSA standards, this model PR222DS/P-LSI R 400 ensures compatibility with rigorous electrical safety requirements, making it suitable for industrial and commercial power distribution systems.

Technical Specification

  • Function: Moulded Case Circuit Breaker, Fixed Four-Pole with Front Terminals.
  • Rated Current (In): 400 A.
  • Rated Operational Voltage: 600 V AC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Interrupting Rating (UL489): 65 kA @ 240 V AC, 25 kA @ 480 V AC, 18 kA @ 600 V AC.
  • Release Type: PR222DS/P-LSI Solid-State Release (EL type).
  • Mechanical Durability: 20,000 cycles at 120 cycles per hour.
  • Terminal Connection: Fixed, front access.
  • Power Loss per Pole: 16.5 W at rated conditions.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T5N 400?
The rated current is 400 A.
What is the maximum operational voltage for this circuit breaker?
The maximum rated operational voltage is 600 V AC.
What type of release does the C.BREAKER TMAX T5N 400 use?
It uses a PR222DS/P-LSI Solid-State Release (EL type).
What is the short-circuit interrupting rating for 240 V AC?
The short-circuit interrupting rating is 65 kA at 240 V AC.
How many mechanical cycles can this breaker endure?
It has a mechanical durability of 20,000 cycles at 120 cycles per hour.
What is the terminal connection type for this circuit breaker?
The terminal connection is fixed with front access.
What is the power loss per pole at rated conditions?
The power loss per pole is 16.5 W at rated conditions.
More Information
Manufacturer Part Number 1SDA060452R1
Barcode 8015644629403
Manufacturer ABB
Number of Poles 4 Pole
Amperage 400A
Alternative Product SKU T5N 400 UL/CSA PR222DS/P-LSI 400 4p F F
Write Your Own Review
You're reviewing:1sda060452r1 t5n 400ul csapr222ds/p-lsi in=400 4 pole abb mccb