Why Choose the Moulded Case Circuit Breaker [1SDA060281R1]

The C.BREAKER TMAX T6S 800 is a fixed three-pole circuit breaker featuring front-access terminals for straightforward installation and maintenance. It incorporates a solid-state release mechanism, providing precise and reliable protection in AC applications. Designed for use with the PR222DS/P-LSIG range, this 800A breaker ensures compatibility and robust performance in demanding electrical distribution systems.

Technical Specification

  • Function: Moulded Case Circuit Breaker, 3-pole fixed with front terminals.
  • Rated Current (In): 800 A.
  • Rated Operational Voltage: 690 V AC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Breaking Capacity (Ics): Up to 85 kA at 220-230 V AC, decreasing to 16.5 kA at 690 V AC.
  • Short-Time Withstand Current (Icw): 10 kA for 1 second.
  • Mechanical Durability: 20,000 cycles at 120 cycles/hour.
  • Electrical Durability: 5,000 cycles at 60 cycles/hour.
  • Terminal Type: Fixed front terminals.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T6S 800?
The rated current is 800 A.
What is the maximum operational voltage for this circuit breaker?
The maximum rated operational voltage is 690 V AC.
What is the short-circuit breaking capacity at 690 V AC?
The short-circuit breaking capacity decreases to 16.5 kA at 690 V AC.
How many mechanical cycles can the circuit breaker endure?
The mechanical durability is rated for 20,000 cycles at 120 cycles/hour.
What type of terminals does the C.BREAKER TMAX T6S 800 have?
It features fixed front terminals.
What is the electrical durability of this circuit breaker?
The electrical durability is rated for 5,000 cycles at 60 cycles/hour.
What standards and approvals does this product conform to?
See the manufacturer's data sheet for standards and approvals.