Why Choose the Moulded Case Circuit Breaker [1SDA054527R1]

The TMAX T4S 250 fixed three-pole circuit breaker features front terminals for straightforward installation and maintenance. Equipped with a solid-state release, it ensures precise and reliable protection in AC applications. This model, Ekip M-LRIU R 200, is engineered for compatibility with a range of industrial electrical systems, delivering consistent performance and enhanced operational safety.

Technical Specification

  • Function: Moulded Case Circuit Breaker, three-pole fixed with front terminals.
  • Rated Operational Voltage: 690 V AC.
  • Rated Current (Iₙ): 200 A.
  • Rated Uninterrupted Current (Iᵤ): 250 A.
  • Short-Circuit Breaking Capacity (Ics / Icu): Up to 85 kA at 220-230 V AC, decreasing to 25 kA at 690 V AC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Terminal Type: Fixed front terminals.
  • Mechanical Durability: 20,000 cycles at 240 cycles per hour.
  • Electrical Durability: 8,000 cycles at 120 cycles per hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated operational voltage of the C.BREAKER TMAX T4S 250?
The rated operational voltage is 690 V AC.
What is the rated current for this circuit breaker?
The rated current (Iₙ) is 200 A.
What is the short-circuit breaking capacity of the TMAX T4S 250?
The short-circuit breaking capacity is up to 85 kA at 220-230 V AC, decreasing to 25 kA at 690 V AC.
How many mechanical cycles can the circuit breaker endure?
The mechanical durability is rated for 20,000 cycles at 240 cycles per hour.
What type of terminals does the TMAX T4S 250 have?
It features fixed front terminals.
What is the rated insulation voltage for this product?
The rated insulation voltage (Ui) is 1000 V.
What standards and approvals does the C.BREAKER TMAX T4S 250 conform to?
See the manufacturer's data sheet for standards and approvals.