The TMAX T4N 320 fixed three-pole circuit breaker features front terminals for straightforward installation and maintenance. Equipped with a solid-state release, it provides precise and reliable protection in AC applications. This model, PR221DS-I R 320, is designed to ensure consistent performance and compatibility within industrial and commercial electrical systems.
Technical Specification
- Function: Moulded Case Circuit Breaker, fixed three-pole with solid-state release.
- Rated Current (In): 320 A.
- Rated Operational Voltage: 690 V AC.
- Number of Poles: 3P.
- Rated Insulation Voltage (Ui): 1000 V.
- Rated Impulse Withstand Voltage (Uimp): 8 kV.
- Short-Circuit Breaking Capacity (Ics and Icu): up to 70 kA at 220-230 V AC, 20 kA at 690 V AC.
- Terminal Type: Fixed front terminals.
- Electrical Durability: 6,000 cycles at 120 cycles/hour.
- Mechanical Durability: 20,000 cycles at 240 cycles/hour.
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What is the rated current of the C.BREAKER TMAX T4N 320?
What is the maximum operational voltage for this circuit breaker?
How many poles does the TMAX T4N 320 have?
What is the short-circuit breaking capacity at 690 V AC?
What type of terminals does this circuit breaker have?
What is the electrical durability of the C.BREAKER TMAX T4N 320?
Is there any conformity information available for this product?
| Manufacturer Part Number | 1SDA054118R1 |
|---|---|
| Barcode | 8015644552176 |
| Manufacturer | ABB |
| Number of Poles | 3 Pole |
| Amperage | 320A |
| Alternative Product SKU | T4N320,1SDA054118R |