Do you need some help?

Call us now on: 01706 242050

1SCA162983R1001 ABB OTHV400E03WP 3 Pole 800VAC to 1000VAC 400A Switch Disconnector

MPN: 1SCA162983R1001

Alt. SKU: OTHV400E03WP

£673.18 £560.98

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the OTHV400E03WP [1SCA162983R1001]

The OTHV-series 3-pole front-operated base-mounted switch disconnector is designed for use in 800 to 1000 VAC systems. It features a robust shaft and handle, both included, ensuring reliable operation and ease of installation in industrial and commercial electrical applications.

Technical Specification

  • Function: 3-pole front operated base mounted switch disconnector.
  • Rated Operational Voltage: 1000 V AC.
  • Rated Operational Current (AC-23A): 200 A at 800 V AC; 400 A at 1000 V AC for AC-21A and AC-22A.
  • Rated Impulse Withstand Voltage (Uimp): 12 kV.
  • Rated Insulation Voltage (Ui): 1000 V according to IEC 60947-1.
  • Degree of Protection: Front IP00.
  • Terminal Type: Lug terminals, 25 mm width.
  • Mechanical Durability: 16,000 operations.
  • Rated Short-Circuit Making Capacity (Icm): 65 kA at 1000 V.
  • Tightening Torque: 30 to 44 N·m per IEC 60947-1.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated operational voltage of the OTHV-series switch disconnector?
The rated operational voltage is 1000 V AC.
What is the maximum rated operational current for this switch disconnector?
The maximum rated operational current is 400 A at 1000 V AC for AC-21A and AC-22A.
What type of terminals does the OTHV-series switch disconnector use?
It uses lug terminals with a width of 25 mm.
What is the degree of protection for this product?
The degree of protection is IP00.
How many operations can the switch disconnector endure mechanically?
The mechanical durability is rated for 16,000 operations.
What is the rated short-circuit making capacity of the switch disconnector?
The rated short-circuit making capacity is 65 kA at 1000 V.
What tightening torque is required for the terminals?
The tightening torque required is between 30 to 44 N·m according to IEC 60947-1.
More Information
Alternative Product SKU OTHV400E03WP
Manufacturer Part Number 1SCA162983R1001
Manufacturer ABB
Barcode 6417019929354
Number of Poles 3 Pole
Max. rated operation voltage Ue AC 1000V
Number of switches 1
Rated operating voltage 1000
Device construction Complete device in housing
Suitable for distribution board installation Yes
Type of control element Other
Colour control element Black
Rated permanent current Iu 400A
Voltage 800-1000VAC
Degree of protection (IP) IP00
Degree of protection (NEMA) Other
Type of electric connection Bolt connection
Packed Quantity 1
Height 220mm
Width 221mm
Depth 107mm
HS Code 85365080
Country of Manufacture Finland
Write Your Own Review
You're reviewing:1SCA162983R1001 ABB OTHV400E03WP 3 Pole 800VAC to 1000VAC 400A Switch Disconnector