Why Choose the OTHV160E12WP [1SCA162951R1001]

The OTHV-series 3-pole front-operated base-mounted switch disconnector is designed for use in 800 to 1000 VAC systems. It features a robust shaft and handle, included for straightforward installation and reliable operation. This switch disconnector ensures secure isolation and is suitable for a range of industrial and commercial electrical applications.

Technical Specification

  • Function: 3-pole front operated base mounted switch disconnector.
  • Rated Voltage: Suitable for 800 to 1000 VAC applications.
  • Rated Operational Current (AC-21A & AC-22A): 160 A at 800 V and 1000 V AC.
  • Rated Operational Current (AC-23A): 135 A at 800 V and 1000 V AC.
  • Rated Impulse Withstand Voltage (Uimp): 12 kV.
  • Rated Insulation Voltage (Ui): 1000 V (IEC 60947-1).
  • Degree of Protection: Front IP00.
  • Terminal Type and Size: Lug terminals, 20 mm width.
  • Mechanical Durability: 20,000 operations.
  • Tightening Torque: 15 to 22 N·m (IEC 60947-1).

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated voltage for the OTHV-series switch disconnector?
The OTHV-series switch disconnector is suitable for applications between 800 to 1000 VAC.
What is the rated operational current for AC-21A and AC-22A?
The rated operational current is 160 A at both 800 V and 1000 V AC.
What is the rated operational current for AC-23A?
The rated operational current is 135 A at both 800 V and 1000 V AC.
What is the degree of protection for this switch disconnector?
The degree of protection is IP00 for the front of the device.
What type of terminals does the OTHV-series use?
The switch disconnector features lug terminals with a width of 20 mm.
What is the mechanical durability of the OTHV-series switch disconnector?
The mechanical durability is rated for 20,000 operations.
What is the tightening torque specification for this product?
The tightening torque should be between 15 to 22 N·m as per IEC 60947-1.
More Information
Alternative Product SKU OTHV160E12WP
Manufacturer Part Number 1SCA162951R1001
Manufacturer ABB
Barcode 6417019929033
Number of Poles 3 Pole
Number of switches 1
Rated operating voltage 1000
Device construction Complete device in housing
Suitable for distribution board installation Yes
Type of control element Other
Colour control element Black
Rated permanent current Iu 200A
Voltage 800-1000VAC
Degree of protection (IP) IP00
Degree of protection (NEMA) Other
Type of electric connection Bolt connection
Packed Quantity 1
Height 170mm
Width 174.5mm
Depth 82.5mm
HS Code 85365080
Country of Manufacture Finland
Write Your Own Review
You're reviewing:1SCA162951R1001 ABB OTHV160E12WP 3 Pole 800VAC to 1000VAC 200A Switch Disconnector