Why Choose the OTHV160E03W [1SCA162946R1001]

The OTHV-series 3-pole front-operated base-mounted switch disconnector is designed for use in 800 to 1000 VAC systems. It provides reliable isolation and switching capabilities for industrial and commercial electrical installations. Please note that the shaft and handle are supplied separately.

Technical Specification

  • Function: 3-pole front operated base mounted switch disconnector.
  • Rated Operational Voltage: 1000 V AC.
  • Rated Operational Current: 160 A (AC-21A and AC-22A at 800–1000 V AC); 135 A (AC-23A at 800–1000 V AC).
  • Rated Insulation Voltage (Ui): 1000 V (IEC 60947-1).
  • Rated Impulse Withstand Voltage (Uimp): 12 kV.
  • Degree of Protection: Front IP00.
  • Terminal Type: Lug terminals, tightening torque 15–22 N·m (IEC 60947-1).
  • Mechanical Durability: 20,000 operations.
  • Short-Circuit Ratings: Making capacity 30 kA, withstand current 8 kA for 1 s.
  • Mounting Type: Base mounting; handle and shaft not included.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated operational voltage of the OTHV-series switch disconnector?
The rated operational voltage is 1000 V AC.
What is the rated operational current for different AC categories?
160 A for AC-21A and AC-22A, and 135 A for AC-23A at 800–1000 V AC.
What type of terminals does the switch disconnector have?
It features lug terminals with a tightening torque of 15–22 N·m.
What is the mechanical durability of the OTHV-series switch disconnector?
The mechanical durability is rated for 20,000 operations.
What is the degree of protection for this switch disconnector?
The degree of protection is IP00 for the front.
What are the short-circuit ratings for this product?
The making capacity is 30 kA, and the withstand current is 8 kA for 1 second.
Is the handle and shaft included with the switch disconnector?
No, the handle and shaft are not included.
More Information
Alternative Product SKU OTHV160E03W
Manufacturer Part Number 1SCA162946R1001
Manufacturer ABB
Barcode 6417019928982
Number of Poles 3 Pole
Max. rated operation voltage Ue AC 1000V
Number of switches 1
Rated operating voltage 1000
Device construction Complete device in housing
Suitable for distribution board installation Yes
Type of control element Other
Rated permanent current Iu 200A
Voltage 800-1000VAC
Degree of protection (IP) IP00
Degree of protection (NEMA) Other
Type of electric connection Bolt connection
Packed Quantity 1
Height 170mm
Width 169.5mm
Depth 82.5mm
HS Code 85365080
Country of Manufacture Finland