We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
11RFN95 - T/O RELAY RFN9 3-5A
MPN: 11RFN95
Alt. SKU: RFN95
Why Choose the 11RFN95?
The Lovato 11RFN95 thermal overload relay safeguards three-phase motors with an operational current of 3–5 A. This non phase-failure (non single-phase sensitive) model features manual resetting and three poles, and mounts directly on BG06, BG09 and BG12 mini-contactors. With IP20 frontal protection, SKU 11RFN95 integrates cleanly into control panels for straightforward, standards-aligned motor protection.
Engineered to recognised international standards, it conforms to IEC/EN 60947-1 and 60947-4-1, UL508 and CSA C22.2 n° 14. Rated Ui 690 V and Uimp 8 kV with Ith 10 A, it operates from -20 to 55 °C up to 3000 m altitude. Direct BG-series mounting enables straightforward integration within industrial panels.
Key Benefits
- Operational current 3-5 A to cover appropriate motor protection.
- Manual reset for controlled restart after an overload event.
- Direct mounting on BG06/BG09/BG12 mini-contactors for tidy integration.
- Three-pole design dedicated to three-phase motor circuits.
- IP20 frontal protection for safer handling inside control panels.
- High insulation and impulse ratings: Ui 690 V; Uimp 8 kV.
- Conforms to IEC/EN, UL and CSA standards for global use.
- Operates -20 to 55 °C and up to 3000 m altitude.
Technical Specification
- Number of poles: 3
- Pollution degree: 3
- IP degree (frontal): IP20
- Rated insulation voltage Ui (IEC/EN): 690 V
- Rated impulse withstand voltage Uimp: 8 kV
- Terminal tightening torque: 2.3 to 2.3 Nm
- Ith (IEC): 10 A
- Operating temperature: -20 to 55 °C
- Storage temperature: -55 to 70 °C
- Max altitude: 3000 m
- Weight: 123 g
What’s Included
- Lovato 11RFN95 thermal overload relay
- Basic installation and adjustment leaflet
- Manufacturer datasheet
Applications
- Three-phase motor protection in industrial control panels
- Direct coupling with BG06, BG09 and BG12 mini-contactors
- OEM and maintenance use requiring IEC/UL/CSA compliant components
- Installations within -20 to 55 °C and up to 3000 m altitude
Frequently Asked Questions
What current range does the Lovato 11RFN95 cover?
Is the relay automatic or manual reset?
Which contactors can it mount on directly?
How many poles and what IP rating does it have?
What standards does it conform to?
Safety note: Install and commission only by qualified personnel. Set within the specified 3–5 A operational current, observe the stated standards and environmental ratings, and isolate power before adjustment.
| Manufacturer Part Number | 11RFN95 |
|---|---|
| Manufacturer | Lovato |
| HS Code | 85364900 |
| Barcode | 8013975020364 |
| Alternative Product SKU | RFN95 |