Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA102443R1 XT5N 400 is a 300 A three-pole fixed moulded case circuit breaker with a TMA thermomagnetic trip unit, 210–300 A thermal adjustment and 1500–3000 A instantaneous protection for UL 489 power-distribution applications.
£957.14
The ABB XT5N 400 TMA 300-3000, order code 1SDA102443R1, is a 3-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT5 range, designed for reliable protection of industrial and commercial low-voltage distribution systems. It combines the compact XT5 frame with a TMA adjustable thermomagnetic trip unit, fixed installation and front terminals.
This UL/CSA configuration has a 300 A rated current and a thermal adjustment range of 210–300 A. Its instantaneous magnetic short-circuit protection is adjustable from 1500–3000 A, allowing the protection characteristics to be coordinated with the connected distribution circuit and downstream equipment.
The XT5N performance level provides an interrupting rating of 35 kA at 480 V AC, with additional UL 489 interrupting ratings across other system voltages. The breaker has a 400 A rated uninterrupted current (Iu), is rated for operation up to 600 V AC, and provides a robust solution for switchboards, distribution panels and industrial electrical systems.
Thermomagnetic circuit breakers combine thermal overload protection with magnetic short-circuit protection. In the ABB XT5N 400 TMA, the adjustable thermal element allows the long-term protection threshold to be configured between 210 A and 300 A, while the magnetic element provides rapid interruption when fault current reaches the selected instantaneous threshold.
With an instantaneous adjustment range of 1500–3000 A and an interrupting rating of 35 kA at 480 V AC, the XT5N provides flexible protection for demanding distribution circuits. Its fixed, front-connected format is designed for efficient integration into industrial switchboards, control panels and power-distribution assemblies.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA102443R1 |
| Product type | Moulded case circuit breaker |
| Frame | XT5 |
| Performance level | N |
| Rated current (In) | 300 A |
| Rated uninterrupted current (Iu) | 400 A |
| Trip unit | TMA thermomagnetic |
| Thermal setting range | 210–300 A |
| Instantaneous short-circuit setting (Ii) | 1500–3000 A |
| Number of poles | 3 |
| Rated operational voltage | 600 V AC / 600 V DC |
| Interrupting rating at 240 V AC | 65 kA |
| Interrupting rating at 480 V AC | 35 kA |
| Interrupting rating at 600 V AC | 18 kA |
| Installation | Fixed |
| Terminal connection | Front |
| Standard | UL 489 |
| Mechanical durability | 20,000 cycles |
| Dimensions (H × W × D) | 205 × 140 × 103.5 mm |
| Power loss | 15.4 W per pole at rated operating conditions |
| EAN / UPC | 8056221021746 |
The ABB 1SDA102443R1 is an XT5N moulded case circuit breaker designed to provide overload and short-circuit protection in industrial and commercial low-voltage power-distribution systems.
The circuit breaker has a rated current of 300 A and a rated uninterrupted current of 400 A.
The thermal protection can be adjusted from 210–300 A, while the instantaneous magnetic short-circuit setting is adjustable from 1500–3000 A.
The XT5N version has an interrupting rating of 35 kA at 480 V AC, with ratings of 65 kA at 240 V AC and 18 kA at 600 V AC.
The 1SDA102443R1 is a fixed 3-pole circuit breaker with front terminals, making it suitable for installation in compatible switchboards and low-voltage distribution assemblies.
ABB SACE Tmax XT moulded case circuit breakers combine compact construction, adjustable protection and dependable fault interruption to protect demanding industrial and commercial low-voltage power-distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.