1SDA075118R1 ABB XT3N 225 TMF 225-2250 3p F F UL/CSA Circuit Breaker

1SDA075118R1 ABB XT3N 225 TMF 225-2250 3p F F UL/CSA Circuit Breaker

ABB 1SDA075118R1 XT3N 225 is a three-pole fixed UL/CSA moulded case circuit breaker with front terminals, a 225 A TMF thermomagnetic release, 2250 A magnetic protection and a 25 kA interruption rating at 480 V AC.

SKU: 1SDA075118R1MPN: 1SDA075118R1
Price
List Price £846.00 ex VAT
Your Price (ex VAT) Save 25%
£634.50 25% OFF
You save £211.50 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £634.50
Trade pricing is personalised to your account

Manufacturer Lead Time

£634.50

Why Choose the ABB XT3N 225 TMF 225-2250 3p F F UL/CSA Circuit Breaker?

The ABB XT3N 225 TMF 225-2250 3p F F UL/CSA, order code 1SDA075118R1, is a robust three-pole moulded case circuit breaker designed for overload and short-circuit protection in low-voltage electrical distribution systems. As part of the ABB SACE Tmax XT / T-Max XT 250 Range, it combines the XT3 frame with dependable thermomagnetic protection for industrial and commercial power distribution applications.

This circuit breaker incorporates an ABB TMF thermomagnetic release with a rated current of 225 A and magnetic protection at 2250 A. The thermal element responds to sustained overload conditions, while the magnetic element provides rapid tripping during high-current short-circuit faults.

The XT3N 1SDA075118R1 features a three-pole fixed construction with front terminals, a rated voltage of 600Y/347 V AC and an N-class interruption rating of 25 kA at 480 V AC. Its UL/CSA configuration makes it suitable for switchboards, distribution panels and industrial electrical assemblies requiring dependable North American circuit protection.

Key Advantages

  • Compact ABB SACE Tmax XT3 moulded case circuit breaker.
  • 225 A TMF thermomagnetic release for overload protection.
  • 2250 A magnetic protection for rapid short-circuit interruption.
  • N-class 25 kA interruption rating at 480 V AC.
  • Three-pole fixed construction for three-phase distribution circuits.
  • Front terminals simplify installation in switchboards and electrical panels.

Key Features

  • ABB SACE Tmax XT3N 225 frame.
  • TMF thermomagnetic trip unit.
  • 225 A rated current.
  • 2250 A magnetic protection level.
  • Three-pole construction.
  • 600Y/347 V AC rated voltage.
  • 25 kA interruption rating at 480 V AC.
  • Fixed mounting.
  • Front terminals for main-circuit connections.
  • UL/CSA configuration for North American electrical distribution applications.

Reliable Thermomagnetic Circuit Protection

The TMF thermomagnetic release combines thermal overload protection with magnetic short-circuit protection in a robust mechanical trip system. This enables the XT3N to protect conductors and connected equipment against both prolonged overcurrent conditions and severe electrical faults without requiring an electronic trip unit.

The ABB Tmax XT3 platform is designed for efficient integration into low-voltage distribution equipment. Its compact frame, fixed construction and front-terminal arrangement make the 1SDA075118R1 a practical solution for industrial switchboards, commercial distribution panels and OEM electrical assemblies.

Typical Applications

  • Industrial low-voltage distribution boards.
  • Commercial electrical switchboards.
  • UL/CSA power distribution assemblies.
  • Feeder and distribution circuit protection.
  • Industrial machinery and control panels.
  • OEM electrical and power distribution systems.

Technical Specifications

Series SACE Tmax XT / T-Max XT 250 Range
ABB order code 1SDA075118R1
Alternate catalogue number XT3NU3225AFF000XXX
Product type Moulded case circuit breaker
Frame size XT3
Frame designation XT3N 225
Trip unit TMF thermomagnetic
Rated current 225 A
Magnetic protection 2250 A
Number of poles 3
Rated voltage 600Y/347 V AC
Interruption rating N, 25 kA at 480 V AC
Mounting type Fixed
Terminal type Front terminals
Certification UL / CSA
EAN 8015644790950
Dimensions (W × H × D) 105 × 150 × 70 mm
Weight approx. 1.7 kg

Frequently Asked Questions

What is the ABB 1SDA075118R1 used for?

It is a three-pole moulded case circuit breaker designed to provide overload and short-circuit protection in low-voltage electrical distribution systems.

What is the rated current of the ABB XT3N 225 TMF 225-2250?

The TMF thermomagnetic trip unit has a rated current of 225 A.

What does 225-2250 mean in the model designation?

The designation identifies the 225 A rated current and 2250 A magnetic protection level of the TMF thermomagnetic release.

What is the interruption rating of ABB 1SDA075118R1?

The XT3N provides an N-class interruption rating of 25 kA at 480 V AC.

How is the ABB XT3N 1SDA075118R1 installed?

This model is a fixed three-pole circuit breaker with front terminals, designed for integration into compatible switchboards, distribution panels and industrial electrical assemblies.

Trusted ABB Circuit Protection

ABB SACE Tmax XT moulded case circuit breakers provide compact and dependable overload and short-circuit protection for industrial and commercial electrical distribution systems, with UL/CSA configurations designed for North American power distribution applications.