2CDS272337R0527 ABB SU202M-K30 30 A 2-Pole K Characteristic Miniature Circuit Breaker 10 kA

2CDS272337R0527 ABB SU202M-K30 30 A 2-Pole K Characteristic Miniature Circuit Breaker 10 kA

ABB SU202M-K30 is a 30 A 2-pole K-characteristic UL 489 miniature circuit breaker with a 10 kA interrupting rating at 480Y / 277 V AC and 96 V DC, designed for branch-circuit protection of industrial loads with elevated starting and inrush currents.

SKU: 2CDS272337R0527Alt SKU: SU202MK30MPN: 2CDS272337R0527
Price
List Price £153.16 ex VAT
Your Price (ex VAT) Save 25%
£114.87 25% OFF
You save £38.29 per unit
Manufacturer Lead Time Estimated Delivery 12 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £114.87
Trade pricing is personalised to your account

Manufacturer Lead Time

£114.87

Why Choose the ABB SU202M-K30 Miniature Circuit Breaker?

The ABB SU202M-K30 is a high-performance 2-pole miniature circuit breaker (MCB) designed for branch-circuit overcurrent and short-circuit protection in industrial electrical, machinery and automation systems. Part of the ABB SU200M series, it combines a 30 A rated current, K tripping characteristic and UL 489 compliance for dependable protection of conductors and connected equipment.

The SU202M-K30 uses thermal-magnetic protection to respond to sustained overloads and short-circuit faults. Its K characteristic is particularly suited to circuits with elevated starting and inrush currents, making it a practical choice for motor loads, transformers, machinery and other inductive equipment where nuisance tripping during normal start-up needs to be minimised.

The breaker provides a 10 kA UL 489 interrupting rating at 480Y / 277 V AC and 96 V DC, together with a 15 kA rated ultimate short-circuit breaking capacity at 400 V AC under IEC 60947-2. ABB order code 2CDS272337R0527 identifies this specific 30 A K-characteristic model within ABB's UL489 / UL1077 MCB product group.

Key Advantages

  • Compact 2-pole miniature circuit breaker for UL 489 branch-circuit protection.
  • 30 A rated current for industrial machinery, control and power circuits.
  • K tripping characteristic suited to loads with elevated starting and inrush currents.
  • 10 kA interrupting rating at 480Y / 277 V AC according to UL 489.
  • 10 kA interrupting rating at 96 V DC for suitable DC branch circuits.
  • Compliance with UL 489, CSA 22.2 No. 5 and IEC/EN 60947-2 supports North American and international machine designs.

Key Features

  • ABB SU200M miniature circuit breaker series.
  • 30 A rated current.
  • 2-pole configuration with two protected poles.
  • K tripping characteristic.
  • 480Y / 277 V AC maximum operating voltage under UL/CSA.
  • 96 V DC maximum operating voltage under UL/CSA.
  • 10 kA UL 489 interrupting rating.
  • 15 kA rated ultimate short-circuit breaking capacity at 400 V AC.
  • 11.2 kA rated service short-circuit breaking capacity at 400 V AC.
  • Red ON / green OFF contact-position indication.

Reliable Protection for Higher-Inrush Industrial Loads

The ABB SU202M-K30 protects conductors and connected equipment against damaging overload and short-circuit currents. Its thermal-magnetic operating principle combines a thermal response to sustained overload conditions with rapid magnetic interruption under short-circuit conditions, while the red and green contact-position indication provides clear visual status.

The K characteristic is particularly useful where normal equipment start-up produces elevated current peaks. This makes the SU202M-K30 well suited to motors, transformers, industrial machinery and other inductive loads when the circuit protection has been correctly selected for the application. Its combination of UL 489, CSA and IEC compliance also supports equipment intended for North American and international markets.

Typical Applications

  • Industrial control panels and electrical cabinets.
  • Motor and inductive-load circuits.
  • Industrial machinery and manufacturing equipment.
  • Factory automation and machine-control systems.
  • Transformer and auxiliary power circuits.
  • Circuits with elevated starting or inrush currents.
  • AC and DC branch-circuit protection applications.

Technical Specifications

Tick the specs you need, then view products that match.

Certification UL 489
Series SU200M
Order code 2CDS272337R0527
EAN 4016779932776
Product type Miniature circuit breaker (MCB)
ABB product group UL489 / UL1077 MCB
Rated current 30 A
Number of poles 2P
Number of protected poles 2
Tripping characteristic K
UL/CSA maximum operating voltage 480Y / 277 V AC
UL/CSA DC maximum operating voltage 96 V DC
UL 489 interrupting rating 10 kA at 480Y / 277 V AC
UL 489 DC interrupting rating 10 kA at 96 V DC
IEC 60947-2 rated operational voltage 400 V AC
Rated ultimate short-circuit breaking capacity 15 kA at 400 V AC
Rated service short-circuit breaking capacity 11.2 kA at 400 V AC
Rated insulation voltage 440 V
Rated impulse withstand voltage 4 kV
Rated frequency 50 / 60 Hz and DC
Power loss 7 W total
Power loss per pole 3.5 W at rated operating conditions
Energy limiting class 3
Electrical endurance 10,000 AC cycles
Mechanical endurance 20,000 cycles
Contact position indication Red ON / Green OFF
Degree of protection IP20
Overvoltage category III
Pollution degree 3
Rigid conductor capacity 0.75–35 mm²
Flexible conductor capacity 0.75–25 mm²
Tightening torque 2.8 N·m
Standards UL 489, CSA 22.2 No. 5, IEC/EN 60947-2
Protection function Branch-circuit overcurrent and short-circuit protection
Mounting type DIN rail
Modular width 2 modules
Dimensions (W × H × D) 35 × 111 × 69 mm
Weight approx. 0.25 kg

Frequently Asked Questions

What is the ABB SU202M-K30 used for?

The ABB SU202M-K30 is a 30 A 2-pole miniature circuit breaker used for branch-circuit overload and short-circuit protection in industrial machinery, control and automation systems, particularly where loads can produce elevated starting or inrush currents.

What voltage and current ratings does the SU202M-K30 have?

The SU202M-K30 has a rated current of 30 A and maximum UL/CSA operating voltages of 480Y / 277 V AC and 96 V DC.

What does the K characteristic mean on the SU202M-K30?

The K tripping characteristic is suited to circuits with elevated normal starting or inrush currents, including appropriate motor, transformer and inductive-load applications, helping to avoid unwanted instantaneous tripping during normal start-up.

What is the interrupting rating of the SU202M-K30?

The SU202M-K30 has a 10 kA UL 489 interrupting rating at 480Y / 277 V AC and 96 V DC. Its rated ultimate short-circuit breaking capacity according to IEC 60947-2 is 15 kA at 400 V AC.

What is the ABB order code for the SU202M-K30?

The ABB order code for the SU202M-K30 is 2CDS272337R0527.

Trusted Industrial Circuit Protection from ABB

ABB SU200M miniature circuit breakers provide compact branch-circuit protection for industrial machinery, control panels and automation systems, combining UL 489 performance with CSA and IEC standards compliance for North American and international applications.