136G4954 Danfoss VLT HVAC Drive 30 kW/40HP 380-480VAC IP55

136G4954 Danfoss VLT HVAC Drive 30 kW/40HP 380-480VAC IP55

Danfoss 136G4954 VLT HVAC Drive FC 102, a 30 kW 40 HP three-phase AC variable frequency drive with IP55 Type 12 protection, mains disconnect and Modbus TCP communication for HVAC pumps, fans, compressors and building automation applications.

SKU: 136G4954Alt SKU: FC-102P30KT4E55H1XGC1XXSXXXXAQBXCXXXXDXMPN: 136G4954
Price
List Price £4,862.00 ex VAT
Your Price (ex VAT) Save 45%
£2,674.10 45% OFF
You save £2,187.90 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,674.10
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,674.10

Danfoss 136G4954 at a glance

The Danfoss 136G4954 is a 30 kW / 40 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B2, IP55 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A1/B (C1), no brake chopper, a graphical LCP 102 control panel, and a Modbus TCP MCA 122 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP55 / UL Type 12 — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A1/B (C1). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Smaller11 kWDanfoss 136G4953IP55 / UL Type 12 · frame B1View drive →
This drive30 kWDanfoss 136G4954IP55 / UL Type 12 · frame B2

Same 30 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 30 kW
Current 52 A
Voltage 480 V
Phase Three Phase
IP Rating IP55
EMC Filter Commercial
Series VLT HVAC Drive FC 102
Full model code FC-102P30KT4E55H1XGC1XXSXXXXAQBXCXXXXDX
Product type AC variable frequency drive
Rated output power 30 kW / 40 HP
Rated current 52 A
Input voltage 380–480 V AC
Input phases 3-phase
Output phases Three phase
Frequency 50 / 60 Hz
Protection rating IP55 / Type 12
Frame size B2
Control panel Graphical local control panel
EMC Filter RFI Class A1/B (C1)
Brake chopper No brake chopper
Communication option Modbus TCP MCA 122
PCB protection Coated PCB
Mains option Mains disconnect
Dimensions (H × W × D) approx. 664 × 243 × 261 mm
Net weight approx. 29.46 kg
EAN 5710108614089

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a Modbus TCP MCA 122 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Can this drive be wall mounted without a panel?

Yes. The IP55 / UL Type 12 enclosure is designed for direct mounting.

Type code decoded

FC-102P30KT4E55H1XGC1XXSXXXXAQBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
30 kW / 40 HPP30K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP55 / UL Type 12E55
RFI filter
Position 16–17
RFI class A1/B (C1)H1
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
Mains disconnect1
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
Modbus TCP MCA 122AQ
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX