135N6210 Danfoss VLT HVAC Drive 110 kW/150HP 380-480VAC IP20

135N6210 Danfoss VLT HVAC Drive 110 kW/150HP 380-480VAC IP20

Danfoss 135N6210 VLT HVAC Drive FC 102, a 110 kW three-phase AC variable speed drive designed for HVAC pumps, fans, compressors and building services applications.

SKU: 135N6210Alt SKU: FC-102N110T4E20H2XGCXXXSXXXXA4BXCXXXXDXMPN: 135N6210
Price
List Price £9,458.00 ex VAT
Your Price (ex VAT) Save 45%
£5,201.90 45% OFF
You save £4,256.10 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,201.90
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,201.90

Danfoss 135N6210 at a glance

The Danfoss 135N6210 is a 110 kW / 150 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame D3H, IP20 / chassis unit, built for mounting inside a control panel or enclosure.

This configuration has RFI class A2 (C3), no brake chopper, a graphical LCP 102 control panel, and a DeviceNet MCA 104 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP20 / chassis — built for mounting inside a control panel or enclosure.
  • EMC: RFI class A2 (C3). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same 110 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 110 kW
Voltage 480 V
Phase Three Phase
IP Rating IP20
EMC Filter Industrial
Series VLT HVAC Drive FC 102
Part number 135N6210
Model code FC-102N110T4E20H2XGCXXXSXXXXA4BXCXXXXDX
Product type AC variable speed drive
Rated output power 110 kW / 150 HP
Input voltage 380–480 V AC
Input phases Three phase
Protection rating IP20 / Chassis
RFI filter Class A2 (C3)
Brake chopper No
Communication option DeviceNet MCA 104
Control panel Graphical Local Control Panel
PCB protection Coated PCB
Frame size D3H
Dimensions (H × W × D) approx. 909 × 250 × 375 mm
Weight approx. 62 kg
EAN 5710108224103

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a DeviceNet MCA 104 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Does this drive need to go in an enclosure?

Yes. IP20 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.

Type code decoded

FC-102N110T4E20H2XGCXXXSXXXXA4BXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
110 kW / 150 HPN110
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP20 / chassisE20
RFI filter
Position 16–17
RFI class A2 (C3)H2
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
DeviceNet MCA 104A4
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option