Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 134N4163 VLT HVAC Drive FC 102, a 132 kW three-phase AC variable frequency drive with IP21 Type 1 mains shield enclosure, Safe Stop, PROFIBUS DP MCA 101, coated PCB, fuse option and RFI Class A1 C2 filter for high-power HVAC motor control applications.
£8,076.75
The Danfoss 134N4163 is a 132 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame D1H, IP21 / UL Type 1 with mains shield unit, suitable for mounting in clean, dry indoor plant rooms.
This configuration has RFI class A1 (C2), safe Stop, no brake chopper, a graphical LCP 102 control panel, and a PROFIBUS DP MCA 101 fieldbus card. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same 132 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 132 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP21 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC 102 | |
| Part Number | 134N4163 | |
| Model Code | FC-102N132T4E2MH4TGC7XXSXXXXA0BXCXXXXDX | |
| Product type | AC variable frequency drive | |
| Rated output power | 132 kW | |
| Horsepower rating | 200 HP | |
| Input voltage | 380-480 V AC | |
| Input phases | Three-phase | |
| Protection rating | IP21 / Type 1 with mains shield | |
| RFI filter | Class A1 (C2) | |
| Safety function | Safe Stop | |
| Communication option | PROFIBUS DP MCA 101 | |
| Control panel | Graphical Local Control Panel | |
| PCB coating | Coated PCB | |
| Mains option | Fuse | |
| Frame size | D1H | |
| Dimensions (H × W × D) | approx. 901 × 325 × 378 mm | |
| Weight | approx. 81 kg | |
| EAN | 5710107894147 |
This unit is fitted with a PROFIBUS DP MCA 101 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.
Yes. The IP21 / UL Type 1 with mains shield enclosure is designed for direct mounting.
FC-102N132T4E2MH4TGC7XXSXXXXA0BXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 132 kW | N132 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP21 / UL Type 1 with mains shield | E2M |
| RFI filter Position 16–17 | RFI class A1 (C2) | H4 |
| Brake / Safe Stop Position 18 | Safe Stop, no brake chopper | T |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Conformal-coated PCBs | C |
| Mains option Position 21 | Fuses | 7 |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | PROFIBUS DP MCA 101 | A0 |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.