134G0081 Danfoss VLT HVAC Drive 132 kW/200HP 380-480VAC IP54

134G0081 Danfoss VLT HVAC Drive 132 kW/200HP 380-480VAC IP54

Danfoss 134G0081 VLT HVAC Drive FC-102 variable frequency drive, 132 kW three phase 380-480 V AC IP54 / Type 12 drive with Safe Stop, PROFIBUS DP MCA 101 option and coated PCB for high-power HVAC motor control applications.

SKU: 134G0081Alt SKU: FC-102N132T4E54H4TGCXXXSXXXXA0BXCXXXXDXMPN: 134G0081
Price
List Price £14,717.00 ex VAT
Your Price (ex VAT) Save 45%
£8,094.35 45% OFF
You save £6,622.65 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,094.35
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,094.35

Danfoss 134G0081 at a glance

The Danfoss 134G0081 is a 132 kW (200 HP) VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame D1H, IP54 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A1 (C2), safe Stop, no brake chopper, a graphical LCP 102 control panel, and a PROFIBUS DP MCA 101 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP54 / UL Type 12 — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A1 (C2). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same 132 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 132 kW
Voltage 480 V
Phase Three Phase
IP Rating IP54
EMC Filter Commercial
Series VLT HVAC Drive FC-102
Part Number 134G0081
Model Code FC-102N132T4E54H4TGCXXXSXXXXA0BXCXXXXDX
Product type AC variable frequency drive
Rated output power 132 kW (200 HP)
Input voltage 380–480 V AC
Input phases 3-phase
Frequency 50 / 60 Hz
Protection rating IP54 / Type 12
RFI filter Class A1 (C2)
Safety function Safe Stop
Communication option PROFIBUS DP MCA 101
Local control panel Graphical LCP
PCB coating Coated PCB
Mains option No mains option
B option No B option
Frame size D1H
Dimensions (H × W × D) approx. 901 × 325 × 378 mm
Net weight approx. 76 kg
EAN 5710107503162

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a PROFIBUS DP MCA 101 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Can this drive be wall mounted without a panel?

Yes. The IP54 / UL Type 12 enclosure is designed for direct mounting.

Type code decoded

FC-102N132T4E54H4TGCXXXSXXXXA0BXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
132 kW (200 HP)N132
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP54 / UL Type 12E54
RFI filter
Position 16–17
RFI class A1 (C2)H4
Brake / Safe Stop
Position 18
Safe Stop, no brake chopperT
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
PROFIBUS DP MCA 101A0
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX