131G8964 Danfoss VLT FC-102 HVAC Drive 22 kW / 30 HP, 380 - 480 VAC, IP55

131G8964 Danfoss VLT FC-102 HVAC Drive 22 kW / 30 HP, 380 – 480 VAC, IP55

Danfoss 131G8964 VLT HVAC Drive FC-102, a 22 kW three-phase AC variable frequency drive designed for HVAC, pump, fan, compressor and refrigeration motor control applications.

SKU: 131G8964Alt SKU: FC-102P22KT4E55H1XNXXXXSXXXXA0BXCXXXXDXMPN: 131G8964
Price
List Price £3,721.00 ex VAT
Your Price (ex VAT) Save 45%
£2,046.55 45% OFF
You save £1,674.45 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,046.55
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,046.55

Danfoss 131G8964 at a glance

The Danfoss 131G8964 is a 22 kW / 30 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B2, IP55 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A1/B (C1), no brake chopper, a numeric LCP 101 control panel, and a PROFIBUS DP MCA 101 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP55 / UL Type 12 — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A1/B (C1). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Same 22 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 22 kW
Voltage 480 V
Phase Three Phase
IP Rating IP55
EMC Filter Commercial
Series VLT® HVAC Drive FC-102
Model code FC-102P22KT4E55H1XNXXXXSXXXXA0BXCXXXXDX
Product type Frequency converter / variable frequency drive
Rated output power 22 kW / 30 HP
Input voltage 380–480 V AC
Input phases Three phase
Frequency 50 / 60 Hz
Protection rating IP55 / Type 12
Mounting type Wall / backplate mounting
Frame size B2
RFI filter Class A1/B (C1)
Brake option No brake chopper
Control panel Numerical local control panel
PCB coating Not coated PCB
Mains option No mains option
A option PROFIBUS DP MCA 101
B option No B option
C1 option No C1 option
D option No D option

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a PROFIBUS DP MCA 101 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Can this drive be wall mounted without a panel?

Yes. The IP55 / UL Type 12 enclosure is designed for direct mounting.

Type code decoded

FC-102P22KT4E55H1XNXXXXSXXXXA0BXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
22 kW / 30 HPP22K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP55 / UL Type 12E55
RFI filter
Position 16–17
RFI class A1/B (C1)H1
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Numeric LCP 101N
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
PROFIBUS DP MCA 101A0
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX