131B6354 Danfoss VLT FC-102 HVAC Drive 22 kW / 30 HP, 380 - 480 VAC, IP21

131B6354 Danfoss VLT FC-102 HVAC Drive 22 kW / 30 HP, 380 – 480 VAC, IP21

Danfoss 131B6354 VLT HVAC Drive FC-102, a 22 kW three phase AC variable frequency drive designed for HVAC motor control, pumps, fans and compressor applications.

SKU: 131B6354Alt SKU: FC-102P22KT4E21H1XNXXXXSXXXXAXBXCXXXXDXMPN: 131B6354
Price
List Price £3,434.00 ex VAT
Your Price (ex VAT) Save 45%
£1,888.70 45% OFF
You save £1,545.30 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,888.70
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,888.70

Danfoss 131B6354 at a glance

The Danfoss 131B6354 is a 22 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is an IP21 / UL Type 1 unit, suitable for mounting in clean, dry indoor plant rooms.

This configuration has RFI class A1/B (C1), no brake chopper, and a numeric LCP 101 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP21 / UL Type 1 — suitable for mounting in clean, dry indoor plant rooms.
  • EMC: RFI class A1/B (C1). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same 22 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 22 kW
Voltage 480 V
Phase Three Phase
IP Rating IP21
EMC Filter Commercial
Series VLT® HVAC Drive FC-102
Type code FC-102P22KT4E21H1XNXXXXSXXXXAXBXCXXXXDX
Product type AC variable frequency drive
Rated output power 22 kW
Motor rating 30 HP
Input voltage 380–480 V AC
Input phases 3-phase
Output phases 3-phase
Frequency 50 / 60 Hz
Protection rating IP21 / Type 1
RFI filter Class A1/B (C1)
Brake chopper No brake chopper
Mains option No mains option
Control panel Numerical Local Control Panel
Dimensions (H × W × D) approx. 664 × 243 × 261 mm
Weight approx. 28.37 kg

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Can this drive be wall mounted without a panel?

Yes. The IP21 / UL Type 1 enclosure is designed for direct mounting.

Type code decoded

FC-102P22KT4E21H1XNXXXXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
22 kWP22K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP21 / UL Type 1E21
RFI filter
Position 16–17
RFI class A1/B (C1)H1
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Numeric LCP 101N
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX