Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
66.82.8.120.0003 Finder Power relay 2pole 30A 120/125V.
The Finder 66.82.8.120.0003 is a high-current electromagnetic power relay from the Finder 66 Series, designed for industrial electrical control, automation and power switching applications. Featuring a 120 V AC operating coil and two changeover contacts (DPDT / 2 CO), it provides flexible control of two independent electrical circuits from a single control signal.
The relay features 30 A normally open (NO) contacts and 10 A normally closed (NC) contacts, making it suitable for applications requiring both high-current switching and changeover functionality. Its silver cadmium oxide (AgCdO) contacts are designed for industrial power switching duties.
The 66.82.8.120.0003 is identified as a Class I, Division 2 / ATEX relay variant and features top flange mounting with Faston 250 quick-connect terminals. These characteristics make it relevant to industrial equipment installations where the applicable electrical and hazardous-location requirements can be satisfied.
This exact model is listed as obsolete by DigiKey. It remains relevant for maintenance and replacement applications, although current stock availability and any proposed substitute should be checked before ordering.
The Finder 66.82.8.120.0003 uses an electromagnetic coil to operate two independent changeover contact sets. When the 120 V AC coil is energised, each contact transfers from its normally closed position to its normally open position. When the coil supply is removed, the return mechanism restores the contacts to their normal positions.
This DPDT configuration allows two circuits to be switched simultaneously while providing both normally open and normally closed outputs. The 30 A NO rating and 10 A NC rating must be considered separately when designing or replacing the relay in an electrical system.
The relay's top flange mounting and Faston 250 terminals provide a practical installation arrangement for compatible industrial equipment. Its AgCdO contacts and non-latching construction support applications requiring repeatable electromechanical switching.
For installations in classified hazardous locations, the .0003 variant's applicable ATEX and Class I, Division 2 markings must be checked against the complete equipment certification and installation conditions. A hazardous-location designation alone does not establish suitability for every explosive atmosphere or installation method.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Load Voltage | 440 V AC | |
| Manufacturer | Finder | |
| Series | 66 Series | |
| Manufacturer part number | 66.82.8.120.0003 | |
| Product type | Electromagnetic power relay | |
| Contact configuration | DPDT / 2 CO / 2 Form C | |
| Number of changeover contacts | 2 | |
| Normally open contact rating | 30 A | |
| Normally closed contact rating | 10 A | |
| Rated contact voltage | 250 V AC | |
| Maximum switching voltage | 440 V AC | |
| Rated AC1 switching capacity (NO) | 7500 VA | |
| Rated AC1 switching capacity (NC) | 2500 VA | |
| Nominal coil voltage | 120 V AC | |
| Coil supply type | AC | |
| Coil resistance | 1.05 kΩ | |
| Nominal coil current | 30 mA | |
| Must-operate voltage | 96 V AC | |
| Must-release voltage | 24 V AC | |
| Contact material | Silver cadmium oxide (AgCdO) | |
| Operating principle | Electromagnetic, non-latching | |
| Operate time | 8 ms | |
| Release time | 15 ms | |
| Operating temperature range | −40 to +70 °C | |
| Mounting type | Top flange / chassis mounting | |
| Terminal type | Faston 250 quick-connect | |
| Terminal width | 6.3 mm | |
| Variant designation | Class I, Division 2 / ATEX | |
| Listed approval agencies | CE, CSA, cURus, EAC, RINA, UKCA and VDE | |
| Product lifecycle | Obsolete, according to DigiKey |
The Finder 66.82.8.120.0003 is an industrial electromagnetic power relay designed for high-current switching, machinery control, automation and auxiliary electrical circuits requiring two changeover contacts.
The relay has a 120 V AC nominal coil voltage. Its control supply must meet the specified AC operating requirements.
The relay has two changeover contacts (2 CO), also described as DPDT or 2 Form C. Each contact set includes normally open and normally closed switching paths.
The relay is rated at 30 A for the normally open contacts and 10 A for the normally closed contacts, subject to the manufacturer's specified switching conditions.
The model is identified as a Class I, Division 2 / ATEX variant. Suitability for a particular hazardous area must be confirmed against the exact certification, equipment marking and installation requirements.
The relay uses silver cadmium oxide (AgCdO) contact material for industrial electrical switching applications.
The relay uses a top flange / chassis mounting arrangement with Faston 250 quick-connect terminals.
The specified operating temperature range is −40 to +70 °C, subject to the manufacturer's installation and operating conditions.
No. It is a non-latching electromagnetic relay. Its changeover contacts return to their normal positions when the coil is de-energised.
The 66.82.8.120.0003 has two changeover contacts (DPDT), while the 66.82.8.120.0303 has two normally open contacts (DPST-NO). They are not automatically interchangeable because their contact arrangements differ.
DigiKey lists the exact model as obsolete and no longer manufactured. Remaining stock may still be available through distributors, but availability should be checked before ordering.
Finder 66 Series power relays are designed for demanding industrial electrical switching applications. The Finder 66.82.8.120.0003 combines a 120 V AC coil, two changeover contacts rated at 30 A NO and 10 A NC, AgCdO contact material and Faston quick-connect terminals in a flange-mounted construction for compatible industrial control installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.