66.82.8.120.0003 Finder Power relay 2pole 30A 120/125V

66.82.8.120.0003 Finder Power relay 2pole 30A 120/125V

66.82.8.120.0003 Finder Power relay 2pole 30A 120/125V.

SKU: 66.82.8.120.0003Alt SKU: 668281200003MPN: 66.82.8.120.0003
This product has been discontinued A direct replacement is available below.
66.82.8.120.4003 Finder Power relay 2pole 30A 120/125V Replacement product 66.82.8.120.4003 Finder Power relay 2pole 30A 120/125V SKU: 66.82.8.120.4003 View

Why Choose the Finder 66.82.8.120.0003 Power Relay?

The Finder 66.82.8.120.0003 is a high-current electromagnetic power relay from the Finder 66 Series, designed for industrial electrical control, automation and power switching applications. Featuring a 120 V AC operating coil and two changeover contacts (DPDT / 2 CO), it provides flexible control of two independent electrical circuits from a single control signal.

The relay features 30 A normally open (NO) contacts and 10 A normally closed (NC) contacts, making it suitable for applications requiring both high-current switching and changeover functionality. Its silver cadmium oxide (AgCdO) contacts are designed for industrial power switching duties.

The 66.82.8.120.0003 is identified as a Class I, Division 2 / ATEX relay variant and features top flange mounting with Faston 250 quick-connect terminals. These characteristics make it relevant to industrial equipment installations where the applicable electrical and hazardous-location requirements can be satisfied.

This exact model is listed as obsolete by DigiKey. It remains relevant for maintenance and replacement applications, although current stock availability and any proposed substitute should be checked before ordering.

Key Advantages

  • 120 V AC operating coil for compatible industrial AC control circuits.
  • Two changeover contacts provide normally open and normally closed switching functions.
  • 30 A normally open contact rating supports appropriately rated high-current loads.
  • 10 A normally closed contact rating provides additional control flexibility.
  • Silver cadmium oxide contacts support industrial power switching applications.
  • Class I, Division 2 / ATEX variant for installations requiring the corresponding certification.
  • Faston 250 quick-connect terminals simplify electrical connections.
  • Top flange mounting supports secure installation in machinery and electrical assemblies.
  • Non-latching electromagnetic operation automatically restores the contacts when the coil is de-energised.
  • −40 to +70 °C operating temperature range supports demanding industrial environments.

Key Features

  • Finder 66 Series industrial power relay.
  • 66.82 flange-mounted relay configuration.
  • 120 V AC nominal coil voltage.
  • Two changeover contacts (2 CO).
  • DPDT / 2 Form C contact arrangement.
  • 30 A normally open contact rating.
  • 10 A normally closed contact rating.
  • 250 V AC rated contact voltage.
  • 440 V AC maximum switching voltage.
  • AgCdO contact material.
  • Class I, Division 2 / ATEX variant designation.
  • Faston 250 quick-connect terminals.
  • Top flange / chassis mounting.
  • Non-latching electromagnetic operating mechanism.
  • 8 ms operate time and 15 ms release time.

High-Current Changeover Switching for Industrial Control Systems

The Finder 66.82.8.120.0003 uses an electromagnetic coil to operate two independent changeover contact sets. When the 120 V AC coil is energised, each contact transfers from its normally closed position to its normally open position. When the coil supply is removed, the return mechanism restores the contacts to their normal positions.

This DPDT configuration allows two circuits to be switched simultaneously while providing both normally open and normally closed outputs. The 30 A NO rating and 10 A NC rating must be considered separately when designing or replacing the relay in an electrical system.

The relay's top flange mounting and Faston 250 terminals provide a practical installation arrangement for compatible industrial equipment. Its AgCdO contacts and non-latching construction support applications requiring repeatable electromechanical switching.

For installations in classified hazardous locations, the .0003 variant's applicable ATEX and Class I, Division 2 markings must be checked against the complete equipment certification and installation conditions. A hazardous-location designation alone does not establish suitability for every explosive atmosphere or installation method.

Typical Applications

  • Industrial automation and machinery control systems.
  • Electrical control panels and power switching assemblies.
  • 120 V AC control circuits.
  • High-current normally open load switching.
  • Changeover switching and auxiliary control functions.
  • Industrial process control equipment.
  • Machinery and equipment interlocking.
  • Industrial heating and load control.
  • Equipment requiring suitably certified hazardous-location components.
  • Maintenance and replacement of compatible legacy Finder 66 Series installations.

Technical Specifications

Tick the specs you need, then view products that match.

Device Type Power Relay
Terminal Type Faston / flat-pin
Load Voltage 440 V AC
Manufacturer Finder
Series 66 Series
Manufacturer part number 66.82.8.120.0003
Product type Electromagnetic power relay
Contact configuration DPDT / 2 CO / 2 Form C
Number of changeover contacts 2
Normally open contact rating 30 A
Normally closed contact rating 10 A
Rated contact voltage 250 V AC
Maximum switching voltage 440 V AC
Rated AC1 switching capacity (NO) 7500 VA
Rated AC1 switching capacity (NC) 2500 VA
Nominal coil voltage 120 V AC
Coil supply type AC
Coil resistance 1.05 kΩ
Nominal coil current 30 mA
Must-operate voltage 96 V AC
Must-release voltage 24 V AC
Contact material Silver cadmium oxide (AgCdO)
Operating principle Electromagnetic, non-latching
Operate time 8 ms
Release time 15 ms
Operating temperature range −40 to +70 °C
Mounting type Top flange / chassis mounting
Terminal type Faston 250 quick-connect
Terminal width 6.3 mm
Variant designation Class I, Division 2 / ATEX
Listed approval agencies CE, CSA, cURus, EAC, RINA, UKCA and VDE
Product lifecycle Obsolete, according to DigiKey

Frequently Asked Questions

What is the Finder 66.82.8.120.0003 used for?

The Finder 66.82.8.120.0003 is an industrial electromagnetic power relay designed for high-current switching, machinery control, automation and auxiliary electrical circuits requiring two changeover contacts.

What coil voltage does the Finder 66.82.8.120.0003 require?

The relay has a 120 V AC nominal coil voltage. Its control supply must meet the specified AC operating requirements.

What contact arrangement does this relay have?

The relay has two changeover contacts (2 CO), also described as DPDT or 2 Form C. Each contact set includes normally open and normally closed switching paths.

What are the normally open and normally closed contact ratings?

The relay is rated at 30 A for the normally open contacts and 10 A for the normally closed contacts, subject to the manufacturer's specified switching conditions.

Is the Finder 66.82.8.120.0003 suitable for hazardous locations?

The model is identified as a Class I, Division 2 / ATEX variant. Suitability for a particular hazardous area must be confirmed against the exact certification, equipment marking and installation requirements.

What contact material does the Finder 66.82.8.120.0003 use?

The relay uses silver cadmium oxide (AgCdO) contact material for industrial electrical switching applications.

How is the Finder 66.82.8.120.0003 mounted?

The relay uses a top flange / chassis mounting arrangement with Faston 250 quick-connect terminals.

What is the operating temperature range?

The specified operating temperature range is −40 to +70 °C, subject to the manufacturer's installation and operating conditions.

Is the Finder 66.82.8.120.0003 a latching relay?

No. It is a non-latching electromagnetic relay. Its changeover contacts return to their normal positions when the coil is de-energised.

What is the difference between Finder 66.82.8.120.0003 and 66.82.8.120.0303?

The 66.82.8.120.0003 has two changeover contacts (DPDT), while the 66.82.8.120.0303 has two normally open contacts (DPST-NO). They are not automatically interchangeable because their contact arrangements differ.

Is the Finder 66.82.8.120.0003 still manufactured?

DigiKey lists the exact model as obsolete and no longer manufactured. Remaining stock may still be available through distributors, but availability should be checked before ordering.

Trusted by Industrial Automation and Electrical Control Professionals

Finder 66 Series power relays are designed for demanding industrial electrical switching applications. The Finder 66.82.8.120.0003 combines a 120 V AC coil, two changeover contacts rated at 30 A NO and 10 A NC, AgCdO contact material and Faston quick-connect terminals in a flange-mounted construction for compatible industrial control installations.