Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
IMO XBF-RD04A is a 4-channel RTD temperature input expansion module for XGB PLC systems supporting Pt100 and JPt100 sensors, -200–600 °C measurement, 40 ms per-channel conversion and sensor disconnection detection.
£376.86
The IMO XBF-RD04A is a dedicated 4-channel RTD temperature input expansion module for compatible IMO XGB programmable logic controller systems. It allows resistance temperature detectors to be connected directly to the PLC, providing accurate digital temperature values for monitoring, control, alarms and process automation.
The XBF-RD04A supports Pt100 and JPt100 RTD sensors using a 3-wire connection. All four channels provide a temperature measurement range of -200–600 °C, with corresponding digital temperature data from -2000–6000 and optional scaled values from 0–4000.
With accuracy of ±0.3% or better at 25 °C, accuracy of ±0.5% or better across 0–55 °C and a conversion speed of 40 ms per channel, the XBF-RD04A provides dependable temperature acquisition for industrial machinery. Digital filtering and automatic sensor-disconnection detection further improve reliability in demanding automation environments.
RTD input modules allow PLC systems to measure temperature directly from resistance temperature detectors without requiring a separate temperature transmitter for each sensor. The IMO XBF-RD04A provides four channels for Pt100 or JPt100 sensors and converts their resistance measurements into digital temperature values that can be processed directly by the PLC program.
The module's 3-wire measurement arrangement helps compensate for resistance introduced by sensor cabling, while configurable digital filtering can reduce unwanted fluctuations in measured temperature. Integrated disconnection detection also identifies open sensor or lead-wire conditions, helping automation systems respond appropriately to instrumentation faults.
Tick the specs you need, then view products that match.
| Current | 04 A | |
|---|---|---|
| Manufacturer | IMO | |
| Series | XGB | |
| Model | XBF-RD04A | |
| Product type | RTD temperature input expansion module | |
| Number of input channels | 4 | |
| Input sensor types | Pt100 / JPt100 | |
| Pt100 standard | JIS C1604-1997 | |
| JPt100 standards | JIS C1604-1981 / KS C1603-1991 | |
| Pt100 temperature range | -200–600 °C | |
| JPt100 temperature range | -200–600 °C | |
| Pt100 digital output | -2000–6000 | |
| JPt100 digital output | -2000–6000 | |
| Scaling display range | 0–4000 | |
| Accuracy at 25 °C | ±0.3% or better | |
| Accuracy across 0–55 °C | ±0.5% or better | |
| Conversion speed | 40 ms per channel | |
| Sensor wiring | 3-wire | |
| Digital filter | 160–64,000 ms | |
| Alarm function | Sensor / lead-wire disconnection detection | |
| Channel-to-channel isolation | Non-isolated | |
| Terminal-to-PLC power isolation | Photocoupler isolation | |
| Terminal block | 15-point removable terminal block | |
| I/O points occupied | 64 points | |
| Internal current consumption | 100 mA at 5 V DC | |
| External current consumption | 100 mA at 24 V DC | |
| External supply | 24 V DC | |
| Status indication | RUN / ALM LEDs | |
| Weight | approx. 63 g | |
| HS Code | 8537109199 | |
| Country of Manufacture | South Korea |
The XBF-RD04A is used to connect RTD temperature sensors directly to compatible IMO XGB PLC systems. It provides four temperature input channels for industrial monitoring, process control, alarms and machine automation.
The XBF-RD04A supports Pt100 and JPt100 RTD sensors. Pt100 sensors are supported to JIS C1604-1997, while JPt100 sensors are supported to JIS C1604-1981 and KS C1603-1991.
The XBF-RD04A measures temperatures from -200–600 °C when used with either supported Pt100 or JPt100 RTD sensors.
The module provides 4 RTD input channels, allowing up to four compatible temperature sensors to be monitored by a single XBF-RD04A module.
Yes. The XBF-RD04A includes per-channel disconnection detection for enabled channels. If a sensor or associated lead wire becomes disconnected, the module can generate a diagnostic condition and its ALM indicator flashes to identify the fault.
IMO XGB temperature input modules provide direct RTD measurement for industrial PLC applications, helping machine builders and automation engineers integrate multi-channel Pt100 and JPt100 temperature monitoring, filtering and sensor diagnostics into compact control systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.