GAX42040A - 4POLE 40A SWITCHED 4TH POLE ADD-ON

GAX42040A – 4POLE 40A SWITCHED 4TH POLE ADD-ON

The Lovato GAX42040A fourth pole add-on accessory upgrades GA016A-GA040A devices to four-pole operation, with simultaneous closing operation as switch poles.

SKU: GAX42040A
Price
List Price £10.03 ex VAT
Your Price (ex VAT) Save 20%
£8.02 20% OFF
You save £2.01 per unit
In stock. Ships today if ordered before 2pm
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8.02
Trade pricing is personalised to your account

5 in stock (can be backordered)

£8.02

Why Choose the GAX42040A?

The Lovato GAX42040A fourth pole add-on accessory upgrades GA016A–GA040A devices to four‑pole operation, with simultaneous closing operation as switch poles. Rated Ith 40 A and suitable for AC use, it supports AC21A, AC22A and AC23A duties. With 1000 V rated insulation (Ui) and 8 kV impulse withstand (Uimp), it delivers robust isolation in compact assemblies.

Engineered for reliability, this module offers 100000 mechanical and AC21A electrical cycles and IP20 frontal protection. It accepts 0.75–16 mm² conductors with 1.8 to 2 Nm terminal torque, operates from -25 to +55 °C, and suits altitudes up to 3000 m. Conforms to IEC/EN 60947-3/-1, UL508, UL98 and CSA C22.2 requirements.

Key Benefits

  • Simultaneous closing with switch poles for reliable four-pole operation.
  • 40 A IEC Ith; robust across AC21A/AC22A/AC23A duties.
  • High insulation: Ui 1000 V with 8 kV impulse withstand.
  • Long life: 100000 mechanical and AC21A electrical cycles.
  • IP20 frontal protection and pollution degree 3 for safer integration.
  • Wide wiring range: 0.75–16 mm², with 1.8–2 Nm torque.
  • Reliable operation from -25 to +55 °C, up to 3000 m.
  • Compatible with Lovato GA016A–GA040A series devices.

What’s Included

  • Lovato GAX42040A fourth pole add-on module
  • Product datasheet (PDF)
  • Basic installation and safety information

Applications

  • Extending Lovato GA016A–GA040A devices to four-pole configurations
  • AC isolation and switching in AC21A and AC22A duty categories
  • Load switching within AC23A limits at 400–690 V
  • Control panels requiring 1000 V insulation and IP20 frontal protection
  • Installations needing simultaneous closing with main switch poles

Technical Specifications

HS Code 85365080
Product type designation GAX42
Number of poles 1
Operating voltage type AC
Ith (IEC) 40 A
Rated insulation voltage Ui (IEC/EN) 1000 V
Rated impulse withstand voltage Uimp 8 kV
Operating current Ie AC21A 400 V 40 A
Operating current Ie AC21A 500 V 40 A
Operating current Ie AC21A 690 V 40 A
Operating current Ie AC22A 400 V 40 A
Operating current Ie AC22A 500 V 40 A
Operating current Ie AC22A 690 V 40 A
Operating current Ie AC23A 400 V 40 A
Operating current Ie AC23A 500 V 25 A
Operating current Ie AC23A 690 V 25 A
Making capacity AC23A 400 V 400 A
Breaking capacity AC23A 400 V 320 A
Mechanical life 100000 cycles
Electrical life AC21A 100000 cycles
Terminal tightening torque 1.8 to 2 Nm
Weight 45 g
Conductor section (IEC) 0.75 to 16 mm²
Operating temperature -25 to +55 °C
Storage temperature -40 to +70 °C
Max altitude 3000 m
IP degree (frontal) IP20
Pollution degree 3

Frequently Asked Questions

Is the GAX42040A compatible with my device?
It is an accessory for GA016A…GA040A versions. Check your device label to confirm the GA…A series.
What current ratings does this fourth pole support?
Ith is 40 A. AC21A and AC22A are 40 A at 400/500/690 V; AC23A is 40 A at 400 V and 25 A at 500/690 V.
Does the fourth pole close at the same time as the main poles?
Yes. It provides simultaneous closing operation as the switch poles for coordinated switching.
What are the installation requirements?
Use 0.75–16 mm² conductors and tighten terminals to 1.8–2 Nm. Always follow the manufacturer’s datasheet.
Which standards and environmental ratings does it meet?
It conforms to IEC/EN 60947-3/-1, UL508, UL98 and CSA C22.2, with IP20 frontal protection and pollution degree 3.

Safety note: Install and service only by qualified personnel. Isolate all power before work and observe specified ratings, wiring ranges and terminal torque.