Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE WV750P8S8 is a 750 VA single-phase wide-input-voltage control transformer with 500-690 V primary voltage taps, dual 0/110/120 V secondary windings configurable for 110/120 V parallel or 220/240 V series output, Class E insulation and 4% voltage regulation.
£105.30
The ETE WV750P8S8 is a robust and versatile 750 VA single-phase wide-input-voltage control transformer designed to provide dependable AC voltage transformation for industrial control circuits, electrical panels and automation equipment. As part of the ETE WV wide-input-voltage control transformer series, it is particularly suitable for electrical panel builders, OEM machinery manufacturers and industrial automation engineers requiring flexible control power supplies from higher-voltage industrial electrical systems.
Featuring 0/500/550/600/690 V primary terminals, the WV750P8S8 accommodates four nominal primary supply voltages through dedicated winding taps. Its two 0/110/120 V secondary windings can be connected in parallel to provide 110 V or 120 V AC, or connected in series to provide 220 V or 240 V AC. This configurable winding arrangement makes the transformer suitable for industrial installations requiring different control circuit operating voltages without changing the transformer model.
With a rated capacity of 750 VA (0.75 kVA), Class E insulation and 4% voltage regulation, the ETE WV750P8S8 provides a practical solution for industrial control power distribution. Its dimensions of 150 × 108 × 145 mm and weight of 7.6 kg support integration into appropriately designed electrical control panels. The specified enclosure reference is EPN 3.
Industrial control transformers convert an available AC supply voltage into a suitable secondary voltage for electrical control circuits and connected equipment. The ETE WV750P8S8 is designed for installations using higher-voltage industrial supplies, with dedicated primary terminals for 500, 550, 600 and 690 V AC. Selecting the appropriate primary winding tap allows the transformer to be configured for the available nominal supply voltage while maintaining the specified secondary winding arrangement.
The transformer's two 0/110/120 V secondary windings provide additional installation flexibility. When correctly connected in parallel, the windings provide a nominal 110 V or 120 V AC output, with the connected load shared between both windings. Alternatively, connecting the windings in series provides a nominal 220 V or 240 V AC output. The total transformer rating remains 750 VA in either configuration. Parallel connections require matching secondary voltage taps and correct winding polarity, while series connections must follow the manufacturer's approved terminal arrangement.
With a specified 4% voltage regulation, the WV750P8S8 offers a relatively small change in secondary voltage between no-load and rated-load conditions, supporting applications where consistent control voltage is important. Its Class E insulation, substantial 750 VA capacity and EPN 3 enclosure reference make it suitable for integration into appropriately designed industrial electrical systems. Correct primary tap selection, secondary winding connections, overload protection, ventilation and installation clearances are essential for reliable operation.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 750 VA | |
|---|---|---|
| Primary Voltage | 0/500/550/600/690V | |
| Secondary Voltage | 0/110/120V + 0/110/120V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Series | WV Wide-Input-Voltage Control Transformers | |
| Model | WV750P8S8 | |
| Product type | Wide-input-voltage control transformer | |
| Transformer configuration | Single-phase | |
| Rated apparent power | 750 VA | |
| Rated capacity | 0.75 kVA | |
| Primary terminals | 0/500/550/600/690 V | |
| Primary voltage options | 500 / 550 / 600 / 690 V AC | |
| Secondary winding 1 | 0/110/120 V | |
| Secondary winding 2 | 0/110/120 V | |
| Secondary winding arrangement | Dual secondary windings | |
| Parallel secondary output | 110 / 120 V AC | |
| Series secondary output | 220 / 240 V AC | |
| Calculated secondary current at 110 V | Approximately 6.82 A in parallel configuration | |
| Calculated secondary current at 120 V | Approximately 6.25 A in parallel configuration | |
| Calculated secondary current at 220 V | Approximately 3.41 A in series configuration | |
| Calculated secondary current at 240 V | Approximately 3.13 A in series configuration | |
| Voltage regulation | 4% | |
| Insulation class | E | |
| Length | 150 mm | |
| Width | 108 mm | |
| Height | 145 mm | |
| Dimensions (L × W × H) | 150 × 108 × 145 mm | |
| Weight | 7.6 kg | |
| Enclosure reference | EPN 3 | |
| Product range | ETE Stock Control Transformers | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE WV750P8S8 is a 750 VA single-phase wide-input-voltage control transformer used to provide 110 V, 120 V, 220 V or 240 V AC supplies for compatible industrial control circuits, electrical panels and automation equipment.
The transformer has a rated apparent power of 750 VA (0.75 kVA). This is the total transformer capacity and does not double when the two secondary windings are connected in parallel.
The transformer features 0/500/550/600/690 V primary terminals, providing dedicated connections for nominal 500, 550, 600 and 690 V AC supplies.
The WV750P8S8 has two 0/110/120 V secondary windings. These can be connected in parallel to provide 110 V or 120 V AC, or in series to provide 220 V or 240 V AC, using the correct winding connections.
Yes. The two secondary windings can be connected in parallel to provide a nominal 110 V or 120 V AC output. Matching voltage taps and correct winding polarity are essential to prevent circulating currents and possible transformer damage.
Yes. By connecting the two 120 V secondary windings correctly in series, the transformer can provide a nominal 240 V AC output. Connecting the two 110 V windings in series provides a nominal 220 V AC output.
Based on its 750 VA rating, the calculated total secondary current is approximately 6.82 A at 110 V, 6.25 A at 120 V, 3.41 A at 220 V or 3.13 A at 240 V. These values are calculated from the rated apparent power and nominal output voltage; actual loading must comply with the manufacturer's winding ratings and installation requirements.
Yes. The transformer includes a dedicated 690 V primary terminal, allowing connection to a compatible nominal 690 V AC supply when correctly installed and protected.
The transformer has a specified 4% voltage regulation, helping maintain a relatively consistent secondary voltage as the connected load changes. This characteristic is useful when selecting control equipment requiring a stable AC supply.
The ETE WV750P8S8 uses Class E insulation, providing a defined thermal insulation classification for operation within the transformer's specified electrical and environmental limits.
The transformer measures 150 × 108 × 145 mm (L × W × H) and weighs 7.6 kg. These dimensions and weight should be considered when planning panel space, mechanical support and wiring access.
The specified enclosure reference is EPN 3. Enclosure selection should also consider the installation environment, ventilation, electrical clearances and required degree of protection.
The transformer is intended for integration into appropriately designed industrial electrical control panels, machinery cabinets and automation systems. Installation should provide suitable mounting, ventilation, earthing arrangements, electrical protection and access to the correct primary and secondary terminal connections.
ETE WV wide-input-voltage control transformers provide a versatile solution for industrial control power applications requiring flexible primary voltage selection and configurable secondary outputs. With four primary voltage taps, dual 110/120 V secondary windings, 4% voltage regulation and a substantial 750 VA capacity, the WV750P8S8 is well suited to electrical panel builders, OEM machinery manufacturers and industrial automation engineers seeking dependable control power transformation from higher-voltage industrial supplies.