Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE WV400P7S7 is a 400 VA single-phase wide-input-voltage control transformer with 380-480 V primary voltage taps, dual 0/24 V secondary windings configurable for 24 V parallel or 48 V series output, Class E insulation and 8% voltage regulation.
£70.20
The ETE WV400P7S7 is a versatile 400 VA single-phase wide-input-voltage control transformer designed to provide reliable low-voltage AC power for industrial control circuits, electrical panels and automation equipment. As part of the ETE WV wide-input-voltage control transformer series, it is suitable for panel builders, OEM machinery manufacturers and industrial electrical engineers requiring flexible voltage transformation across multiple industrial supply voltages.
Featuring 0/380/400/420/440/460/480 V primary terminals, the WV400P7S7 accommodates six nominal primary supply voltages through dedicated winding taps. Its two 0/24 V secondary windings can be connected in parallel to provide a 24 V AC output or connected in series to provide a 48 V AC output. This flexible secondary configuration makes the transformer particularly useful for industrial installations requiring either 24 V or 48 V control power.
With a rated capacity of 400 VA (0.4 kVA), Class E insulation and 8% voltage regulation, the ETE WV400P7S7 provides a practical solution for industrial control power distribution. Its dimensions of 120 × 108 × 120 mm and weight of 5.5 kg allow integration into suitably designed electrical control panels. The specified enclosure references are EPH 3 or EPN 2.
Industrial control transformers convert an available AC supply voltage into a suitable secondary voltage for control circuits and electrical equipment. The ETE WV400P7S7 provides a flexible solution for installations using nominal primary voltages of 380, 400, 420, 440, 460 or 480 V AC. By selecting the appropriate primary terminal, the transformer can be configured for the available industrial supply without requiring a different transformer model for each listed voltage.
The transformer's two 0/24 V secondary windings provide additional installation flexibility. When correctly connected in parallel, the windings supply a nominal 24 V AC output, with the load shared between the two windings. Alternatively, connecting the windings in series provides a nominal 48 V AC output. The total transformer rating remains 400 VA in either configuration. Parallel connections require correct winding polarity and matching voltage taps, while series connections must follow the manufacturer's approved terminal arrangement.
The specified 8% voltage regulation should be considered when selecting connected equipment, particularly where the secondary load varies during operation. Its Class E insulation, practical dimensions and EPH 3 or EPN 2 enclosure references support integration into appropriately designed industrial electrical installations. Correct primary tap selection, secondary wiring, overload protection and ventilation are important for dependable transformer operation.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 400 VA | |
|---|---|---|
| Primary Voltage | 0/380/400/420/440/460/480V | |
| Secondary Voltage | 0/24V + 0/24V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Series | WV Wide-Input-Voltage Control Transformers | |
| Model | WV400P7S7 | |
| Product type | Wide-input-voltage control transformer | |
| Transformer configuration | Single-phase | |
| Rated apparent power | 400 VA | |
| Rated capacity | 0.4 kVA | |
| Primary terminals | 0/380/400/420/440/460/480 V | |
| Primary voltage options | 380 / 400 / 420 / 440 / 460 / 480 V AC | |
| Secondary winding 1 | 0/24 V | |
| Secondary winding 2 | 0/24 V | |
| Secondary winding arrangement | Dual secondary windings | |
| Parallel secondary output | 24 V AC | |
| Series secondary output | 48 V AC | |
| Rated secondary current at 24 V | Approximately 16.67 A, based on 400 VA total capacity | |
| Rated secondary current at 48 V | Approximately 8.33 A, based on 400 VA total capacity | |
| Voltage regulation | 8% | |
| Insulation class | E | |
| Length | 120 mm | |
| Width | 108 mm | |
| Height | 120 mm | |
| Dimensions (L × W × H) | 120 × 108 × 120 mm | |
| Weight | 5.5 kg | |
| Enclosure reference | EPH 3 or EPN 2 | |
| Product range | ETE Stock Control Transformers | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE WV400P7S7 is a 400 VA single-phase wide-input-voltage control transformer used to provide 24 V or 48 V AC supplies for compatible industrial control circuits, electrical panels and automation equipment.
The transformer has a rated apparent power of 400 VA (0.4 kVA). This is the total transformer capacity and does not double when the two secondary windings are connected in parallel.
The transformer features 0/380/400/420/440/460/480 V primary terminals, providing dedicated connections for nominal 380, 400, 420, 440, 460 and 480 V AC supplies.
The WV400P7S7 has two 0/24 V secondary windings. These can be connected in parallel to provide 24 V AC or in series to provide 48 V AC, using the correct winding connections.
Yes. The two 24 V secondary windings can be connected in parallel to provide a nominal 24 V AC output. Correct winding polarity is essential to prevent circulating currents and possible transformer damage.
Yes. By connecting the two 24 V secondary windings correctly in series, the transformer can provide a nominal 48 V AC output. The total rated capacity remains 400 VA.
Based on its 400 VA rating, the calculated total secondary current is approximately 16.67 A at 24 V in parallel configuration or 8.33 A at 48 V in series configuration. These values are calculated from the rated apparent power and nominal output voltage; actual loading must comply with the manufacturer's winding ratings and installation requirements.
The transformer has a specified 8% voltage regulation. This characteristic should be considered when designing control circuits and selecting equipment sensitive to variations in secondary supply voltage.
The ETE WV400P7S7 uses Class E insulation, providing a defined thermal insulation classification for operation within the transformer's specified electrical and environmental limits.
The transformer measures 120 × 108 × 120 mm (L × W × H) and weighs 5.5 kg. These dimensions should be considered when planning panel space, mounting arrangements and wiring access.
The specified enclosure references are EPH 3 or EPN 2. Final enclosure selection should account for the installation environment, ventilation, electrical clearances and required degree of protection.
Yes. The transformer includes a dedicated 480 V primary terminal, allowing connection to a compatible nominal 480 V AC supply when correctly installed and protected.
The transformer is intended for integration into appropriately designed industrial electrical control panels, machinery cabinets and automation systems. Installation should provide suitable mounting, ventilation, earthing arrangements, electrical protection and access to the correct primary and secondary terminal connections.
ETE WV wide-input-voltage control transformers provide a versatile solution for industrial control power applications requiring flexible primary voltage selection and configurable secondary outputs. With six primary voltage taps, dual 24 V secondary windings and a robust 400 VA capacity, the WV400P7S7 is well suited to electrical panel builders, OEM machinery manufacturers and industrial automation engineers seeking dependable 24 V or 48 V AC control power.
We use cookies