Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE WV3000P7S7 is a 3000 VA single-phase wide-input-voltage control transformer with selectable 380–480 V AC primary taps, dual 0/24 V secondary windings configurable for 24 V parallel or 48 V series output, Class E insulation and 3% voltage regulation.
£330.45
The ETE WV3000P7S7 is a high-capacity 3000 VA (3 kVA) single-phase wide-input-voltage control transformer designed for industrial electrical control panels, machinery, switchgear and automation systems. Part of the ETE WV wide-input-voltage control transformer range, it combines multiple primary voltage taps with configurable dual secondary windings, providing flexible AC voltage conversion for industrial installations requiring substantial low-voltage control power capacity.
The WV3000P7S7 features a 0/380/400/420/440/460/480 V primary terminal arrangement, supporting compatible 380, 400, 420, 440, 460 and 480 V AC supplies. Its two 0/24 V secondary windings can be connected in parallel for 24 V AC or in series for 48 V AC. This flexible output configuration makes the transformer suitable for industrial control systems with different low-voltage AC operating requirements.
With a rated apparent power of 3000 VA (3 kVA), Class E insulation and 3% voltage regulation, the WV3000P7S7 provides a practical solution for appropriately rated industrial control circuits. Its dimensions of 192 × 189 × 185 mm and weight of 28 kg require suitable installation space and secure mechanical support. The specified enclosure reference is EPN 5.
The ETE WV3000P7S7 is designed for industrial control installations where the available primary supply voltage may differ between machines, facilities or electrical systems. Its selectable primary terminals support 380, 400, 420, 440, 460 and 480 V AC, allowing the transformer to be configured for several compatible industrial supply voltages.
The transformer incorporates two secondary windings, each with 0/24 V terminals. Connecting the two matching secondary windings in parallel with the correct polarity provides 24 V AC. Connecting the windings in series with the correct additive polarity provides 48 V AC. All winding connections must follow ETE's instructions to ensure correct voltage selection and safe operation.
Based on its 3000 VA rating, the theoretical full-load secondary current is approximately 125 A at 24 V AC or 62.5 A at 48 V AC. These calculated values assume the full rated apparent power is available in the selected configuration. Actual permissible winding currents and loading requirements must follow ETE's specifications.
The specified 3% voltage regulation means secondary voltage variation between operating load conditions should be considered when selecting connected equipment. The potentially high secondary currents require particular attention to conductor sizing, terminal ratings, circuit protection and distribution arrangements. Correct primary tap selection, secondary winding polarity and appropriate installation clearances are essential for safe operation. Due to its 28 kg weight, the transformer also requires suitable mechanical support and safe handling during installation.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 3000 VA | |
|---|---|---|
| Primary Voltage | 0/380/400/420/440/460/480V | |
| Secondary Voltage | 0/24V + 0/24V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Series | WV Wide-Input-Voltage Control Transformers | |
| Model | WV3000P7S7 | |
| Product type | Wide-input-voltage control transformer | |
| Rated apparent power | 3000 VA (3 kVA) | |
| Number of phases | Single-phase | |
| Primary terminal arrangement | 0/380/400/420/440/460/480 V | |
| Primary voltage options | 380/400/420/440/460/480 V AC | |
| Secondary terminal arrangement | 0/24 V + 0/24 V | |
| Secondary winding configuration | Dual windings, series or parallel | |
| Parallel secondary output | 24 V AC | |
| Series secondary output | 48 V AC | |
| Voltage regulation | 3% | |
| Insulation class | E | |
| Length | 192 mm | |
| Width | 189 mm | |
| Height | 185 mm | |
| Dimensions (L × W × H) | 192 × 189 × 185 mm | |
| Weight | 28 kg | |
| Enclosure reference | EPN 5 | |
| Product range reference | ETE Stock Control Transformer Range, March 2026 |
The ETE WV3000P7S7 is a 3000 VA single-phase wide-input-voltage control transformer designed to convert compatible 380–480 V AC supplies into selectable 24 V or 48 V AC outputs for industrial control circuits, machinery and automation equipment.
The transformer features a 0/380/400/420/440/460/480 V primary terminal arrangement, supporting selectable 380, 400, 420, 440, 460 and 480 V AC supply connections.
The transformer provides 24 V AC when its two secondary windings are connected in parallel, or 48 V AC when they are connected in series.
The transformer has a rated apparent power of 3000 VA (3 kVA), making it suitable for appropriately rated higher-capacity industrial control, signalling and automation applications.
The two 0/24 V secondary windings must be connected according to ETE's wiring instructions. Parallel operation requires correct matching and polarity to obtain 24 V AC, while series operation requires the correct additive-polarity connection to obtain 48 V AC.
Based on the 3000 VA rating, the theoretical full-load secondary current is approximately 125 A at 24 V AC or 62.5 A at 48 V AC, assuming the full rating is available in the selected configuration. Actual permissible loading must follow ETE's specifications.
The specified 3% voltage regulation describes the transformer's secondary voltage variation between load conditions. Connected equipment should tolerate the resulting voltage variation, and additional regulation may be required for voltage-sensitive devices.
The transformer measures 192 mm long × 189 mm wide × 185 mm high and weighs 28 kg. Installation requires adequate cabinet space, secure mechanical support and suitable handling arrangements.
The transformer features Class E insulation and specifies EPN 5 as its enclosure reference. The appropriate enclosure and mounting arrangement should be selected according to installation requirements.
The ETE WV3000P7S7 combines a 3000 VA (3 kVA) rating, six selectable primary voltage taps, configurable 24 V and 48 V AC secondary outputs, Class E insulation and 3% voltage regulation. Its wide-input-voltage design makes it a practical choice for industrial control panel builders, OEM machinery manufacturers and electrical maintenance engineers requiring flexible, high-capacity low-voltage AC control power.