ETE WV250P8S8 is a 250 VA single-phase wide-input-voltage control transformer with selectable 500 V, 550 V, 600 V or 690 V primary connections, dual 110/120 V secondary windings configurable for 110/120 V parallel or 220/240 V series output, Class E insulation and 8% voltage regulation.
£53.70
The ETE WV250P8S8 is a versatile 250 VA single-phase wide-input-voltage control transformer designed to provide reliable electrical isolation and flexible AC control power for industrial machinery, electrical panels and automation systems. Part of the ETE WV Wide Input Voltage transformer series, it features primary terminals marked 0/500/550/600/690 V and two separate secondary windings with terminals marked 0/110/120 V + 0/110/120 V.
Manufactured by Eastern Transformers & Equipment (ETE), the WV250P8S8 is suitable for industrial installations operating from nominal 500 V, 550 V, 600 V or 690 V AC supplies. Its dual-secondary winding arrangement allows 110 V AC or 120 V AC parallel connections, or 220 V AC or 240 V AC series connections, providing useful flexibility for different control circuit requirements.
With a rated capacity of 250 VA, Class E insulation and 8% voltage regulation, this transformer provides a practical solution for electrical control systems requiring selectable supply and output voltages. Measuring 120 × 88 × 120 mm and weighing 3.9 kg, the WV250P8S8 is suitable for integration into industrial control equipment, with EPH 3 or EPN 2 specified as enclosure references.
The ETE WV250P8S8 is designed for electrical installations where several higher industrial supply voltages may be encountered. Its primary winding includes terminals marked 0/500/550/600/690 V, allowing the installer to select the appropriate nominal voltage connection for the available supply.
This arrangement makes the transformer particularly useful for OEM machinery manufacturers, industrial panel builders and equipment suppliers working with installations that operate at different supply voltages. Rather than requiring a separate transformer model for every nominal supply, the WV250P8S8 provides several primary connection options within one product.
The primary voltage terminals are discrete winding taps, not an automatic voltage-ranging input. The correct primary connection must be selected before energising the transformer, and installation must follow the manufacturer's wiring instructions and applicable electrical safety requirements.
A key feature of the WV250P8S8 is its dual-secondary winding configuration. The transformer incorporates two separate windings, each with terminals marked 0/110/120 V, allowing the output to be configured for different industrial control voltages.
The 250 VA rating applies to the complete transformer and must not be interpreted as 250 VA available independently from each secondary winding. Parallel connections require correctly matched voltage taps and winding polarity, while series connections must be arranged for the intended combined output voltage.
All secondary connections should be made in accordance with ETE's wiring instructions, including appropriate winding phasing, load assessment and circuit protection.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 250 VA | |
|---|---|---|
| Primary Voltage | 0/500/550/600/690V | |
| Secondary Voltage | 0/110/120V + 0/110/120V | |
| Phase | Single Phase | |
| Manufacturer | Eastern Transformers & Equipment (ETE) | |
| Series | WV Wide Input Voltage Transformers | |
| Model | WV250P8S8 | |
| Product type | Wide-input-voltage control transformer | |
| Transformer configuration | Single-phase | |
| Rated apparent power | 250 VA | |
| Primary terminals | 0/500/550/600/690 V | |
| Primary voltage options | 500, 550, 600 or 690 V AC | |
| Primary voltage connections | Discrete voltage taps selected to match the nominal supply | |
| Secondary terminals | 0/110/120 V + 0/110/120 V | |
| Secondary winding arrangement | Two separate 110/120 V tapped windings | |
| Parallel secondary output | 110 V AC or 120 V AC | |
| Series secondary output | 220 V AC or 240 V AC | |
| Output connection | 110/120 V parallel or 220/240 V series | |
| Voltage regulation | 8% | |
| Insulation class | E | |
| Enclosure reference | EPH 3 or EPN 2 | |
| Length | 120 mm | |
| Width | 88 mm | |
| Height | 120 mm | |
| Dimensions (L × W × H) | 120 × 88 × 120 mm | |
| Weight | 3.9 kg | |
| Manufacturer range | ETE stock control transformer range | |
| Specification reference | ETE stock control transformer price list, March 2026 |
The ETE WV250P8S8 is a 250 VA single-phase wide-input-voltage control transformer used to provide isolated 110 V AC, 120 V AC, 220 V AC or 240 V AC power for compatible industrial control circuits and electrical equipment.
The transformer has primary terminals marked 0/500/550/600/690 V, providing nominal input connections for 500, 550, 600 or 690 V AC supplies. The correct voltage tap must be selected for the available supply.
The WV250P8S8 has two separate secondary windings with terminals marked 0/110/120 V + 0/110/120 V. These can be connected in parallel for 110 V AC or 120 V AC, or in series for 220 V AC or 240 V AC.
The two secondary windings are connected in parallel using matching 110 V or 120 V taps and the correct winding polarity. ETE's connection instructions must be followed to ensure correct phasing and current sharing.
The secondary windings are connected in series with the correct polarity. Using the corresponding 110 V taps provides a nominal 220 V AC output, while the 120 V taps provide a nominal 240 V AC output.
The transformer has a rated apparent power of 250 VA. This is the total transformer capacity, not an individual 250 VA rating for each secondary winding.
The transformer has a specified 8% voltage regulation, describing the change in secondary voltage between the manufacturer's defined loading conditions.
The WV250P8S8 measures 120 × 88 × 120 mm (L × W × H) and weighs 3.9 kg.
The transformer features Class E insulation. The manufacturer's specified enclosure references are EPH 3 or EPN 2, which can be used when confirming a suitable protective enclosure for the installation.
ETE WV wide-input-voltage transformers provide flexible primary supply connections, dependable electrical isolation and adaptable secondary winding arrangements for industrial control applications. The WV250P8S8 combines a 250 VA rating, selectable 500/550/600/690 V primary connections and 110/120 V parallel or 220/240 V series secondary outputs with Class E insulation and 8% voltage regulation, making it a practical choice for professional electrical panel builders and industrial equipment manufacturers.