ETE MV750P2S3 is a 750 VA single-phase multi-voltage control transformer with 20/0/380/420 V primary terminals, dual 12 V secondary windings configurable for 12 V parallel or 24 V series output, Class E insulation and 4% voltage regulation.
£101.10
The ETE MV750P2S3 is a robust and versatile 750 VA single-phase multi-voltage control transformer designed to provide reliable low-voltage AC power for industrial machinery, electrical control panels and automation systems. As part of the ETE MV multi-voltage control transformer series, it combines a multi-terminal primary winding arrangement with dual 12 V secondary windings for flexible industrial control voltage applications.
The MV750P2S3 features 20/0/380/420 V primary terminals and two separate 0/12 V secondary windings. These secondary windings can be connected in parallel to provide a nominal 12 V AC output or in series to provide a nominal 24 V AC output. This flexibility makes the transformer suitable for machine builders, electrical panel manufacturers and industrial maintenance engineers requiring configurable control voltage supplies.
With a rated apparent power of 750 VA, Class E insulation and 4% voltage regulation, the MV750P2S3 offers dependable voltage transformation for compatible industrial control circuits. Its dimensions of 150 × 108 × 145 mm support installation in suitable electrical control enclosures. The transformer also includes a 20 V primary adjustment tap, with the correct connection arrangement to be confirmed with ETE before installation.
Industrial control transformers such as the ETE MV750P2S3 convert an incoming AC supply into a lower voltage suitable for electrical control circuits, automation equipment and industrial machinery. The MV750P2S3 incorporates primary terminals marked 20/0/380/420 V and two independent 12 V secondary windings, providing flexibility for different low-voltage AC control requirements.
The two secondary windings can be connected in parallel for a nominal 12 V AC output or in series for a nominal 24 V AC output. Correct winding polarity must be observed, particularly when connecting the windings in parallel. The transformer's 750 VA apparent-power rating applies to the total rated secondary loading and must be considered when selecting connected equipment.
The MV750P2S3 also includes a 20 V primary adjustment tap for the manufacturer's specified voltage adjustment arrangement. The exact primary terminal connections must be confirmed with ETE before energising the transformer. Its Class E insulation, 4% voltage regulation and robust construction make it a practical solution for industrial control panels and machine-building applications. Suitable circuit protection, ventilation and enclosure arrangements should be provided during installation.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 750 VA | |
|---|---|---|
| Primary Voltage | 20/0/380/420V | |
| Secondary Voltage | 0/12V + 0/12V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Series | MV Multi-Voltage Control Transformers | |
| Model | MV750P2S3 | |
| Product type | Industrial multi-voltage control transformer | |
| Transformer type | Single-phase | |
| Rated apparent power | 750 VA | |
| Primary terminals | 20/0/380/420 V | |
| Primary voltage terminals | 380/420 V | |
| Primary adjustment tap | 20 V | |
| Primary connection note | Confirm adjustment tap connections with ETE | |
| Secondary terminals | 0/12 V + 0/12 V | |
| Secondary winding arrangement | Dual 12 V windings | |
| Parallel output connection | 12 V AC | |
| Series output connection | 24 V AC | |
| Insulation class | E | |
| Voltage regulation | 4% | |
| Length | 150 mm | |
| Width | 108 mm | |
| Height | 145 mm | |
| Dimensions (L × W × H) | 150 × 108 × 145 mm | |
| Weight | 7.6 kg | |
| Enclosure reference | EPN 3 | |
| Product range reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV750P2S3 is a 750 VA single-phase multi-voltage control transformer designed to provide 12 V or 24 V AC supplies for compatible industrial control circuits, machinery and automation equipment.
The transformer has a rated apparent power of 750 VA, which applies to the total rated secondary loading.
The transformer features 20/0/380/420 V primary terminals, including a 20 V adjustment tap. The correct supply and adjustment connections must be confirmed with ETE.
Yes. Its two separate 0/12 V secondary windings can be connected in parallel for a nominal 12 V AC output or in series for a nominal 24 V AC output, using the correct winding polarity and connection arrangement.
The 20 V primary adjustment tap is provided for the manufacturer's specified primary voltage adjustment arrangement. The exact terminal connections must be confirmed with ETE before installation.
The transformer measures 150 × 108 × 145 mm (length × width × height) and weighs 7.6 kg.
The MV750P2S3 features Class E insulation and a specified 4% voltage regulation.
The specified enclosure reference is EPN 3. The selected enclosure should be checked for suitable installation dimensions, ventilation and environmental protection.
The ETE MV multi-voltage control transformer range provides flexible voltage transformation solutions for industrial electrical installations. The MV750P2S3 combines a 750 VA rating, dual 12 V secondary windings, configurable 12 V or 24 V AC outputs and 4% voltage regulation to support dependable industrial machinery and automation control applications.
The ETE MV1000P1S1 is a robust and versatile 1000 VA single-phase multi-voltage control transformer designed to provide reliable AC control power for industrial machinery, electrical control panels and automation systems. Part of the ETE MV multi-voltage control transformer series, it features a multi-terminal primary winding and selectable secondary voltage taps for flexible industrial electrical installations.
The MV1000P1S1 incorporates 10/0/220/240 V primary terminals and 0/55/110 V secondary terminals, allowing selection of either a nominal 55 V or 110 V AC output. This makes the transformer suitable for compatible industrial control systems where different AC control voltages may be required. Electrical isolation between the primary and secondary windings also supports its use as a dedicated control circuit supply.
With a rated apparent power of 1000 VA (1 kVA), Class E insulation and 4% voltage regulation, the MV1000P1S1 provides a practical solution for industrial control applications requiring a higher-capacity transformer. Its dimensions of 150 × 125 × 145 mm support integration into suitable electrical control enclosures. The transformer also includes a 10 V primary adjustment tap, with the correct connections to be confirmed with ETE.
The ETE MV1000P1S1 is designed to convert a compatible incoming AC supply into a selected secondary voltage for industrial machinery and electrical control circuits. Its primary terminals are marked 10/0/220/240 V, while the secondary winding features 0/55/110 V taps, providing flexible output voltage selection for compatible industrial equipment.
The secondary terminal arrangement allows selection of either a nominal 55 V AC output or a nominal 110 V AC output using the appropriate tap. Its 1000 VA (1 kVA) apparent-power rating provides a defined capacity for suitably selected control circuit loads. The total connected loading must remain within the transformer's rated operating limits, and any individual tap loading must comply with the manufacturer's requirements.
The MV1000P1S1 also incorporates a 10 V primary adjustment tap for the manufacturer's specified voltage adjustment arrangement. The exact primary terminal connections must be confirmed with ETE before energising the transformer. Its Class E insulation, 4% voltage regulation and robust construction make it suitable for integration into industrial control panels and machinery cabinets with appropriate circuit protection, ventilation and enclosure arrangements.
The ETE MV1000P1S1 is a 1000 VA single-phase multi-voltage control transformer designed to provide selectable 55 V or 110 V AC supplies for compatible industrial machinery, electrical control circuits and automation equipment.
The transformer has a rated apparent power of 1000 VA (1 kVA), which must be considered when selecting connected control circuit loads.
The transformer features 10/0/220/240 V primary terminals, including a 10 V adjustment tap. The correct primary supply and adjustment connections must be confirmed with ETE.
Yes. The transformer features 0/55/110 V secondary terminals, allowing a nominal 55 V or 110 V AC output to be selected through the appropriate secondary tap.
The 10 V primary adjustment tap provides a manufacturer-specified voltage adjustment facility. The exact terminal connection arrangement must be confirmed with ETE before installation.
The transformer measures 150 × 125 × 145 mm (length × width × height) and weighs 9.8 kg.
The MV1000P1S1 features Class E insulation and a specified 4% voltage regulation.
The specified enclosure reference is EPN 3. The selected enclosure should provide suitable installation space, ventilation and environmental protection for the transformer.
The ETE MV multi-voltage control transformer range provides flexible and reliable AC voltage transformation for industrial machinery and electrical control systems. The MV1000P1S1 combines a 1000 VA rating, selectable 55 V or 110 V AC secondary taps and 4% voltage regulation to support dependable operation in industrial control panels and automation applications.