Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE MV750P1S1 is a 750 VA single-phase multi-voltage control transformer with 10/0/220/240 V primary terminals, selectable 55 V or 110 V AC secondary taps, Class E insulation, 4% voltage regulation and an EPN 3 enclosure reference.
£101.10
The ETE MV750P1S1 is a 750 VA single-phase multi-voltage control transformer designed for industrial control panels, electrical machinery and automation systems requiring reliable AC control power. Part of the ETE MV Multi-Voltage Series, it features 10/0/220/240 V primary terminals and 0/55/110 V secondary terminals, providing flexible voltage connections for industrial electrical installations.
With nominal 220 V and 240 V primary connections and selectable 55 V or 110 V AC secondary taps, the MV750P1S1 is suitable for appropriately rated control circuits, including industrial relays, contactors, signalling equipment and machinery controls.
The transformer combines a 750 VA rated capacity, Class E insulation and 4% voltage regulation. Its dimensions are 150 × 108 × 145 mm, with a weight of 7.6 kg and a specified enclosure reference of EPN 3.
Important installation note: The primary winding incorporates a 10 V adjustment tap. Confirm the exact terminal connections and adjustment method with ETE before installation or energisation.
The ETE MV750P1S1 features a 10/0/220/240 V primary terminal arrangement, providing flexibility for industrial electrical systems using the manufacturer's specified primary supply connections.
The terminals marked 220 V and 240 V support corresponding nominal supply arrangements when connected according to ETE's approved wiring diagram. The additional 10 V terminal forms part of the primary adjustment arrangement.
This configuration is useful for electrical panel builders and machinery manufacturers producing control systems for different nominal AC supply voltages.
Installation requirement: Confirm the exact 10 V primary adjustment tap connections with ETE before energising the transformer. Do not infer an adjustment method from the terminal markings alone.
The MV750P1S1 incorporates 0/55/110 V secondary terminals, providing nominal 55 V AC and 110 V AC connections for compatible industrial control equipment.
When connected for nominal 110 V AC output, the transformer's 750 VA rating corresponds to a calculated secondary current of approximately 6.82 A.
This configuration is suitable for appropriately rated industrial control circuits, including contactors, relays, switching equipment and machinery control devices.
The intermediate secondary terminal provides a nominal 55 V AC output connection, supporting compatible equipment requiring a lower control voltage.
Dividing the transformer's 750 VA rating by 55 V produces a theoretical current of approximately 13.64 A. However, this calculation does not establish the permissible loading of the individual 55 V winding section.
Engineering consideration: Confirm the maximum allowable 55 V tap current and any simultaneous loading restrictions with ETE before designing the control circuit.
The MV750P1S1 has a specified 4% voltage regulation characteristic. Voltage regulation describes the change in secondary voltage as the electrical load varies under the relevant operating conditions.
This characteristic is important when selecting control equipment with defined voltage tolerances, particularly industrial contactors, relays and switching devices that may impose short-duration inrush loads.
The 750 VA rating should be considered alongside the connected equipment's steady-state consumption, energisation requirements and permissible voltage range. The rating must not be assumed to apply independently to every secondary tap.
The ETE MV750P1S1 measures 150 mm in length, 108 mm in width and 145 mm in height, with a specified weight of 7.6 kg. These dimensions and weight should be considered when planning control panel layouts and selecting suitable mounting supports.
The transformer has Class E insulation and a specified enclosure reference of EPN 3. The complete installation should provide appropriate mechanical support, ventilation and protection for the intended operating environment.
Primary and secondary circuit protection, conductor sizing, protective earthing and terminal connections should be designed in accordance with applicable electrical installation requirements and ETE's technical instructions.
Before commissioning, verify the primary adjustment tap arrangement, selected secondary voltage and permissible winding loading using the manufacturer's approved documentation.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 750 VA | |
|---|---|---|
| Primary Voltage | 10/0/220/240V | |
| Secondary Voltage | 0/55/110V | |
| Phase | Single Phase | |
| Brand | ETE | |
| Manufacturer part number | MV750P1S1 | |
| Product series | MV Multi-Voltage Series | |
| Product category | Control Transformers | |
| Transformer type | Multi-voltage control transformer | |
| Phase configuration | Single-phase | |
| Rated apparent power | 750 VA | |
| Primary terminals | 10/0/220/240 V | |
| Primary voltage markings | 220 V and 240 V, with an additional 10 V adjustment terminal | |
| Primary adjustment tap | 10 V — confirm connections with ETE | |
| Secondary terminals | 0/55/110 V | |
| Secondary output connections | 55 V AC or 110 V AC taps | |
| Calculated secondary current at 110 V | Approximately 6.82 A, based on 750 VA | |
| 55 V tap loading | Permissible current requires ETE confirmation | |
| Insulation class | E | |
| Voltage regulation | 4% | |
| Length | 150 mm | |
| Width | 108 mm | |
| Height | 145 mm | |
| Dimensions (L × W × H) | 150 × 108 × 145 mm | |
| Weight | 7.6 kg | |
| Enclosure reference | EPN 3 | |
| Manufacturer catalogue | ETE Stock Control Transformer Range | |
| Catalogue date | March 2026 |
The ETE MV750P1S1 is a 750 VA single-phase multi-voltage control transformer designed to supply compatible industrial control circuits requiring nominal 55 V AC or 110 V AC. Typical applications include machinery control panels, contactors, relays and automation equipment.
The transformer features 10/0/220/240 V primary terminals, including a 10 V adjustment tap. The correct connections must be confirmed with ETE and selected according to the manufacturer's approved wiring diagram.
Yes. The transformer has 0/55/110 V secondary terminals, providing nominal 55 V AC and 110 V AC output connections. The permissible loading of the 55 V tap must be confirmed with ETE.
At the full 750 VA rating, the calculated nominal secondary current is approximately 6.82 A at 110 V AC. The connected load and any switching inrush requirements should also be considered.
Not without manufacturer confirmation. The 750 VA rating applies to the transformer but does not independently establish the permissible current or apparent power available from the individual 55 V winding section. Confirm the tap loading limits with ETE.
The 10 V primary adjustment tap forms part of the transformer's multi-voltage winding arrangement. Its exact function and terminal connections must be confirmed with ETE before installation or energisation.
The transformer measures 150 × 108 × 145 mm, weighs 7.6 kg, has Class E insulation and 4% voltage regulation, and has a specified enclosure reference of EPN 3.
The ETE MV750P1S1 combines a 750 VA rating, 10/0/220/240 V primary terminals and selectable 55 V or 110 V secondary connections in a single-phase industrial control transformer. With Class E insulation, 4% voltage regulation and an EPN 3 enclosure reference, it provides a flexible solution for electrical panel builders, OEM machinery manufacturers and industrial maintenance engineers. Confirm the 10 V primary adjustment tap connections and permissible secondary tap loading with ETE before commissioning.
We use cookies