Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE MV7500P2S2 is a 7500 VA (7.5 kVA) single-phase multi-voltage control transformer with 20/0/380/420V primary terminals, 10/0/220/240V secondary terminals, tapped output per datasheet, a 10V adjustment tap requiring terminal confirmation with ETE, Class F insulation, 2% voltage regulation, ETS 1 enclosure reference, dimensions of 300 x 330 x 330 mm and a weight of 70 kg.
£660.75
The ETE MV7500P2S2 is a heavy-duty 7500 VA (7.5 kVA) single-phase multi-voltage control transformer designed for industrial electrical installations requiring substantial control and auxiliary AC power capacity. Part of the ETE MV multi-voltage control transformer range, it features primary terminals marked 20/0/380/420V and secondary terminals marked 10/0/220/240V, providing a tapped voltage arrangement for applications where the transformer connections must be matched to the available supply and required output.
With a rated apparent power of 7500 VA, the MV7500P2S2 is suited to consideration for larger industrial control panels, machinery installations and compatible auxiliary electrical systems. Its secondary arrangement includes 220 V and 240 V terminal markings, together with a 10 V adjustment tap. The precise output connection is specified as tapped output per datasheet, and the adjustment tap must not be interpreted or wired without confirming the correct terminal arrangement with ETE.
The transformer combines Class F insulation with a specified 2% voltage regulation, providing useful technical characteristics for industrial load planning. Measuring 300 × 330 × 330 mm and weighing 70 kg, it is a substantial electrical component requiring careful consideration of mechanical support, installation access, lifting arrangements and ventilation. Its listed ETS 1 enclosure reference should be checked against the relevant ETE documentation when planning the complete installation.
The ETE MV7500P2S2 is intended for industrial electrical systems requiring a substantial transformer capacity and a tapped voltage arrangement. Its primary terminals are marked 20/0/380/420V, while its secondary terminals are marked 10/0/220/240V. These markings identify the transformer's available terminal positions, but they should not be treated as a complete wiring diagram. The actual connections must follow the ETE datasheet and the manufacturer's terminal identification instructions.
The multi-voltage arrangement can be useful where equipment specifications require a particular AC control voltage and the available supply must be matched to the transformer's approved input connections. The secondary terminal markings include 220 V and 240 V, while the product specification also identifies a 10 V adjustment tap. The adjustment tap's electrical relationship to the other terminals must be verified before use. It should not be assumed that the 10 V terminal can simply be added to or subtracted from a selected output without manufacturer confirmation.
The 7500 VA rated apparent power provides a substantial capacity for compatible industrial loads. As a theoretical sizing reference, dividing 7500 VA by 220 V gives approximately 34.09 A, while dividing 7500 VA by 240 V gives approximately 31.25 A. These calculations illustrate the relationship between apparent power and nominal voltage; they are not independently stated manufacturer output current ratings. Actual permissible current, tap selection and loading must be checked against the ETE datasheet and applicable operating limits.
The specified 2% voltage regulation is an important characteristic for electrical system design. Transformer voltage regulation generally describes the change in secondary voltage between specified load conditions, commonly comparing no-load and rated-load operation. A 2% regulation figure does not mean that the transformer actively stabilises the output or guarantees a fixed ±2% voltage tolerance under every supply and loading condition. The expected voltage at connected equipment should be evaluated using the manufacturer's data and the actual installation conditions.
The MV7500P2S2 uses Class F insulation, a thermal insulation classification relevant to transformer construction and operating conditions. Class F does not establish a Class II electrical protection classification, an ingress protection rating or any specific environmental suitability. Similarly, the ETS 1 enclosure reference identifies the enclosure arrangement stated in the ETE catalogue but does not independently confirm an IP rating. Any enclosure selection, ventilation provision or environmental protection requirement should be verified using ETE's documentation.
At 70 kg, the transformer requires appropriate handling and installation planning. The supporting structure must be capable of carrying the transformer's weight, and suitable lifting methods, access clearances and mechanical fixing arrangements should be established before installation. Electrical design must also account for suitable primary and secondary circuit protection, conductor sizing, thermal management and the demands of connected equipment. Installation and commissioning should be undertaken by suitably qualified personnel in accordance with ETE's instructions and applicable electrical requirements.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 7500 VA | |
|---|---|---|
| Primary Voltage | 20/0/380/420V | |
| Secondary Voltage | 10/0/220/240V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Product range | MV Multi-Voltage Control Transformers | |
| Model / SKU | MV7500P2S2 | |
| Product type | Multi-voltage control transformer | |
| Phase configuration | Single-phase | |
| Rated apparent power | 7500 VA | |
| Rated apparent power (kVA) | 7.5 kVA | |
| Primary terminals | 20/0/380/420V | |
| Secondary terminals | 10/0/220/240V | |
| Output connection | Tapped output per datasheet | |
| Adjustment tap note | 10 V adjustment tap; confirm terminal connections with ETE | |
| Insulation class | F | |
| Voltage regulation | 2% | |
| Length | 300 mm | |
| Width | 330 mm | |
| Height | 330 mm | |
| Dimensions (L × W × H) | 300 × 330 × 330 mm | |
| Weight | 70 kg | |
| Enclosure reference | ETS 1 | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV7500P2S2 is a 7500 VA (7.5 kVA) single-phase multi-voltage control transformer intended for compatible industrial control and auxiliary AC power applications. It features tapped primary and secondary terminal arrangements that must be connected according to ETE's datasheet.
The transformer has a rated apparent power of 7500 VA, equivalent to 7.5 kVA. Connected loads must remain within the manufacturer's permitted operating limits.
The transformer has primary terminals marked 20/0/380/420V. The correct input connection and the function of each terminal must be verified using the ETE datasheet before energising the transformer.
The secondary terminals are marked 10/0/220/240V. The product's output connection is specified as tapped output per datasheet, so the correct terminal arrangement must be confirmed with ETE.
The transformer has secondary terminals marked 220V and 240V, but the required output connection must be established from the manufacturer's datasheet. The correct terminal selection depends on the approved wiring arrangement and the intended application.
The specification identifies a 10 V adjustment tap associated with the secondary terminal arrangement. Its intended connection and effect on output voltage must be confirmed with ETE. The terminal markings alone are not sufficient to determine the correct adjustment wiring.
The stated 2% voltage regulation describes secondary voltage variation between specified loading conditions. It does not mean the transformer actively regulates voltage or guarantees a fixed ±2% output tolerance under all conditions.
The MV7500P2S2 has Class F insulation. This is a thermal insulation classification and should not be confused with an electrical protection classification such as Class II.
The transformer measures 300 × 330 × 330 mm (length × width × height) and weighs 70 kg. Suitable handling equipment and mechanical support should be provided during installation.
The ETE catalogue lists ETS 1 as the enclosure reference. This designation should be checked against ETE's documentation and does not independently establish an ingress protection rating.
At a nominal 220 V output, 7500 VA divided by 220 V gives approximately 34.09 A. At a nominal 240 V output, the equivalent calculation gives approximately 31.25 A. These are theoretical sizing references, not independently stated manufacturer current ratings. The actual permissible output current and tapped connections must be verified against ETE's datasheet.
The ETE MV7500P2S2 delivers 7500 VA (7.5 kVA) rated apparent power in a single-phase multi-voltage control transformer with 20/0/380/420V primary terminals and 10/0/220/240V secondary terminals. Featuring Class F insulation, 2% voltage regulation and an ETS 1 enclosure reference, it is a practical option for substantial industrial control and auxiliary power applications. The 10 V adjustment tap and all output terminal connections must be confirmed with ETE before installation or commissioning.