ETE MV500P2S3 is a 500 VA single-phase multi-voltage industrial control transformer with 20/0/380/420 V primary terminals and dual 0/12 V secondary windings. Its secondary output can be configured for 12 V AC in parallel or 24 V AC in series. The 20 V primary adjustment tap connections must be confirmed with ETE. Class E insulation, 8% voltage regulation, dimensions of 120 x 120 x 120 mm, weight of 6.2 kg and EPH 3 or EPN 2 enclosure references.
£74.33
The ETE MV500P2S3 is a 500 VA single-phase multi-voltage industrial control transformer featuring a tapped primary winding and two nominal 12 V AC secondary windings. Part of the ETE MV stock control transformer range, this model provides flexible AC control power for compatible industrial electrical panels, OEM machinery and automation systems.
The transformer features 20/0/380/420 V primary terminals and 0/12 V + 0/12 V secondary terminals. Its two secondary windings can be connected in parallel to provide a nominal 12 V AC output or in series to provide a nominal 24 V AC output. This makes the MV500P2S3 a practical option for electrical designers working with different low-voltage AC control requirements.
The MV500P2S3 also includes a 20 V primary adjustment tap. The correct function of this tap and its approved terminal connections must be confirmed with ETE. The primary terminal markings should not be used alone to determine the wiring arrangement.
With a 500 VA apparent power rating, Class E insulation and 8% voltage regulation, the MV500P2S3 is suitable for consideration in industrial control applications with appropriately rated electrical loads. It measures 120 × 120 × 120 mm and has a specified weight of 6.2 kg.
The transformer is listed in the ETE Stock Control Transformer Range, March 2026, with enclosure references of EPH 3 or EPN 2.
The ETE MV500P2S3 has a tapped primary winding with terminals marked 20/0/380/420 V. This arrangement is intended for compatible AC supply configurations using the appropriate manufacturer-approved connections.
The 20 V primary adjustment tap forms part of this winding arrangement. Its exact purpose and the approved terminal combinations must be confirmed with ETE before the transformer is energised. The 20 V marking must not be treated as evidence of an independently rated 20 V primary input.
Electrical designers should verify the intended supply voltage and primary terminal arrangement against the manufacturer's wiring diagram. Incorrect primary connections can result in an unsuitable secondary voltage, excessive current or equipment damage.
The MV500P2S3 incorporates two separate 0/12 V secondary windings. These windings provide flexibility for industrial control circuits requiring either a nominal 12 V AC or 24 V AC supply.
When the two secondary windings are correctly connected in parallel, the nominal output voltage remains at 12 V AC. Parallel operation allows the windings to share the connected load within the transformer's overall 500 VA rating.
Correct winding polarity is essential. Incorrect parallel connections can create excessive circulating current, overheating or transformer damage. The manufacturer's approved terminal connections must always be followed.
When the two secondary windings are correctly connected in series, their nominal voltages add together to provide 24 V AC.
The series connection must use the correct winding polarity so the two 12 V outputs add rather than oppose one another. The ETE wiring diagram should be used to establish the appropriate connections.
The 12 V and 24 V options are alternative configurations of the same transformer, not two independent 500 VA supplies.
The ETE MV500P2S3 has a total rated apparent power of 500 VA. The nominal current corresponding to each secondary voltage can be calculated using:
Current (A) = Apparent power (VA) ÷ Secondary voltage (V)
For a correctly connected 12 V AC parallel output:
500 VA ÷ 12 V = approximately 41.67 A
This is the calculated total current corresponding to the complete transformer rating at 12 V AC. It does not independently establish the manufacturer's permissible terminal or winding current ratings.
For a correctly connected 24 V AC series output:
500 VA ÷ 24 V = approximately 20.83 A
This is the calculated current corresponding to the complete transformer rating at 24 V AC.
The connected load must remain within the applicable transformer and winding ratings. Engineers should also assess the operating characteristics, inrush requirements and appropriate circuit protection for connected equipment.
The ETE MV500P2S3 has a specified 8% voltage regulation. Voltage regulation describes the change in secondary voltage between no-load and rated-load conditions under defined operating or test conditions.
The actual secondary voltage may vary with the applied primary supply and connected load. The nominal 12 V AC and 24 V AC outputs should not be interpreted as electronically stabilised voltages.
When selecting the transformer for voltage-sensitive equipment, engineers should consider its regulation characteristic and the expected variation in the primary supply.
Before installing the ETE MV500P2S3, confirm the available primary supply, required secondary voltage, total connected apparent power and correct terminal connections.
Primary wiring: The 20/0/380/420 V terminals include a 20 V adjustment tap. Confirm the approved primary terminal connections with ETE before energising the transformer.
Secondary wiring: The two 0/12 V secondary windings must be connected in parallel for a nominal 12 V AC output or in series for a nominal 24 V AC output. Correct winding polarity is essential in both configurations.
Suitable primary and secondary circuit protection, conductor sizing, protective earthing where applicable, ventilation and secure mechanical mounting should be incorporated into the installation design.
The specified EPH 3 or EPN 2 enclosure references should be checked against the intended installation requirements. The references alone do not establish an enclosure protection rating or confirm that an enclosure is included.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 500 VA | |
|---|---|---|
| Primary Voltage | 20/0/380/420V | |
| Secondary Voltage | 0/12V + 0/12V | |
| Phase | Single Phase | |
| Brand | ETE | |
| Series | MV Multi-Voltage Stock Control Transformer Range | |
| Model / SKU | MV500P2S3 | |
| Product type | Industrial multi-voltage control transformer | |
| Transformer configuration | Tapped primary and dual secondary windings | |
| Number of phases | Single-phase | |
| Rated apparent power | 500 VA | |
| Primary terminals | 20/0/380/420 V | |
| Primary adjustment tap | 20 V | |
| Primary connection note | Confirm connections with ETE | |
| Secondary terminals | 0/12 V + 0/12 V | |
| Secondary winding arrangement | Two nominal 12 V AC windings | |
| Parallel secondary output | 12 V AC | |
| Series secondary output | 24 V AC | |
| Output connection | 12 V parallel or 24 V series | |
| Insulation class | E | |
| Voltage regulation | 8% | |
| Calculated nominal current at 12 V AC | Approximately 41.67 A total, based on 500 VA | |
| Calculated nominal current at 24 V AC | Approximately 20.83 A, based on 500 VA | |
| Length | 120 mm | |
| Width | 120 mm | |
| Height | 120 mm | |
| Dimensions (L × W × H) | 120 × 120 × 120 mm | |
| Weight | 6.2 kg | |
| Enclosure reference | EPH 3 or EPN 2 | |
| Product range reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV500P2S3 is a 500 VA single-phase multi-voltage control transformer intended for compatible industrial control panels, OEM machinery and auxiliary electrical circuits. Its dual secondary windings provide selectable 12 V AC or 24 V AC output configurations.
The primary terminals are specified as 20/0/380/420 V. The correct connections, including the 20 V adjustment tap, must be confirmed with ETE.
The MV500P2S3 includes a 20 V primary adjustment tap as part of its tapped primary winding. Its exact function and approved terminal connections must be confirmed with ETE before installation.
The secondary terminals are specified as 0/12 V + 0/12 V, representing two separate nominal 12 V AC secondary windings.
Yes. The two secondary windings can be connected in parallel to provide a nominal 12 V AC output, provided the correct winding polarity and manufacturer's wiring instructions are followed.
Yes. The two secondary windings can be connected in series to provide a nominal 24 V AC output, with the correct winding polarity so their voltages add together.
The ETE MV500P2S3 has a rated apparent power of 500 VA. This rating applies to the complete transformer rather than separately to each secondary winding.
At a nominal 12 V AC output, the 500 VA rating corresponds to approximately 41.67 A total when the secondary windings are correctly connected in parallel. This is a calculated value for load assessment.
At a nominal 24 V AC output, the 500 VA rating corresponds to approximately 20.83 A when the secondary windings are correctly connected in series. This is a calculated value for load assessment.
The MV500P2S3 has a specified Class E insulation system.
The ETE MV500P2S3 has a specified 8% voltage regulation. This should be considered when assessing the operating voltage requirements of connected equipment.
The transformer measures 120 mm long, 120 mm wide and 120 mm high, with a specified weight of 6.2 kg.
The specified enclosure references are EPH 3 or EPN 2. Final enclosure selection should account for installation conditions, dimensions, ventilation and applicable electrical requirements.
Correct winding polarity is essential when connecting the two 12 V secondary windings in series or parallel. Incorrect connections can cause opposing voltages, excessive circulating current or transformer damage. Always follow the ETE connection diagram.
No. The ETE MV500P2S3 provides a nominal 12 V AC or 24 V AC output, depending on the secondary winding configuration. Equipment requiring DC power needs a suitable DC power supply or appropriate rectification and conditioning equipment.
The MV500P2S3 has a 20/0/380/420 V primary terminal arrangement incorporating a 20 V adjustment tap. Confirming the ETE connection diagram helps prevent incorrect wiring and ensures the intended primary configuration is selected.
When selecting the ETE MV500P2S3, verify that the intended primary supply can be accommodated using the manufacturer's approved terminal arrangement. The 20 V primary adjustment tap must be connected only in accordance with ETE's instructions.
Next, determine whether the connected equipment requires a nominal 12 V AC or 24 V AC supply. The two secondary windings must be configured correctly in parallel or series, with the appropriate polarity.
The transformer's 500 VA rating, 8% voltage regulation, Class E insulation, 120 × 120 × 120 mm dimensions and 6.2 kg weight should all be considered during electrical and mechanical design.
The ETE MV500P2S3 combines a 500 VA rating with a tapped 20/0/380/420 V primary and dual 12 V secondary windings. Its selectable 12 V AC parallel or 24 V AC series output, Class E insulation and 8% voltage regulation make it a practical option for compatible industrial control panels and OEM machinery. Always confirm the 20 V primary adjustment tap connections with ETE.