ETE MV500P1S1 is a 500 VA single-phase multi-voltage control transformer with 10/0/220/240 V primary terminals, selectable 55 V or 110 V AC secondary taps, a 10 V primary adjustment tap requiring ETE connection confirmation, Class E insulation and 8% voltage regulation.
£74.33
The ETE MV500P1S1 is a 500 VA single-phase multi-voltage control transformer designed for industrial electrical installations requiring flexible primary voltage connections and selectable secondary control voltages. Part of the ETE MV multi-voltage transformer series, it features 10/0/220/240 V primary terminals and 0/55/110 V secondary terminals, providing a practical solution for applications requiring nominal 55 V AC or 110 V AC control power.
The MV500P1S1 supports 220 V and 240 V primary voltage selections through its appropriately marked terminals, while the secondary winding offers selectable 55 V or 110 V output taps. This flexibility makes the transformer suitable for industrial control panels, machinery installations, automation systems and electrical equipment requiring compatible AC control voltages.
The primary winding also incorporates a 10 V adjustment tap, providing an additional connection facility within the multi-voltage arrangement. The correct use of this adjustment tap and the required primary terminal connections must be confirmed with ETE before installation. The terminal markings alone should not be used to assume an unverified voltage adjustment or wiring configuration.
With Class E insulation, 8% voltage regulation, dimensions of 120 × 120 × 120 mm and a weight of 6.2 kg, the ETE MV500P1S1 offers a compact, versatile control transformer solution. Its associated enclosure references are EPH 3 or EPN 2, supporting suitable enclosure selection during electrical panel design.
The ETE MV500P1S1 provides a practical solution for industrial installations requiring dedicated AC control power from a compatible 220 V or 240 V supply. Its 10/0/220/240 V primary terminal arrangement allows selection of the appropriate nominal primary voltage, while the 0/55/110 V secondary terminals provide two control voltage options for compatible connected equipment.
The 55 V AC output can be selected using the appropriate secondary tap for compatible industrial control circuits. Alternatively, the 110 V AC output supports equipment designed for that nominal supply voltage. Both options are derived from the transformer's tapped secondary winding, and the 500 VA rating applies to the transformer as a whole. The output taps should not be treated as two independently rated 500 VA supplies, and simultaneous loading of both taps should not be assumed without manufacturer confirmation.
The 10 V primary adjustment tap provides an additional connection facility within the primary winding arrangement. Because the terminals are marked 10/0/220/240 V, the correct use of the adjustment tap must be confirmed with ETE before the transformer is energised. Incorrect primary connections may result in unsuitable secondary voltages or damage to connected equipment. Installation should follow the manufacturer's approved connection diagram rather than assumptions based solely on terminal markings.
At the rated 500 VA capacity, the calculated secondary current is approximately 9.09 A at 55 V AC or 4.55 A at 110 V AC. These figures are calculated by dividing the apparent power rating by the nominal secondary voltage and are not separately verified manufacturer current ratings. The actual current capability must also be considered alongside the selected tap arrangement, winding limits, connected load characteristics and manufacturer's instructions.
The specified 8% voltage regulation is relevant when evaluating secondary voltage variation between load conditions. Actual output voltage depends on the selected primary connection, incoming supply voltage and connected load. Control relays, contactor coils, solenoids and other inductive devices may also introduce starting or inrush requirements, so both continuous apparent power and short-duration operating demands should be considered when selecting the transformer.
With Class E insulation, dimensions of 120 × 120 × 120 mm and a weight of 6.2 kg, the MV500P1S1 can be incorporated into appropriately engineered industrial control assemblies. Its EPH 3 or EPN 2 enclosure references assist with enclosure planning. Suitable mechanical support, primary and secondary circuit protection, conductor sizing, ventilation and electrical clearances should be provided in accordance with ETE installation instructions and applicable electrical requirements.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 500 VA | |
|---|---|---|
| Primary Voltage | 10/0/220/240V | |
| Secondary Voltage | 0/55/110V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Product series | MV Multi-Voltage Control Transformers | |
| Manufacturer part number | MV500P1S1 | |
| Product type | Multi-voltage control transformer | |
| Transformer configuration | Single-phase | |
| Rated apparent power | 500 VA | |
| Rated capacity | 0.5 kVA | |
| Primary terminals | 10/0/220/240 V | |
| Nominal primary voltage options | 220 V or 240 V AC | |
| Primary adjustment tap | 10 V | |
| Primary adjustment connection requirement | Confirm correct terminal connections with ETE | |
| Secondary terminals | 0/55/110 V | |
| Secondary output option 1 | 55 V AC | |
| Secondary output option 2 | 110 V AC | |
| Secondary output connection | 55 V or 110 V taps | |
| Calculated secondary current at 55 V | Approximately 9.09 A at 500 VA | |
| Calculated secondary current at 110 V | Approximately 4.55 A at 500 VA | |
| Calculated ideal primary current at 220 V | Approximately 2.27 A at 500 VA, excluding transformer losses and magnetising current | |
| Calculated ideal primary current at 240 V | Approximately 2.08 A at 500 VA, excluding transformer losses and magnetising current | |
| Insulation class | E | |
| Voltage regulation | 8% | |
| Length | 120 mm | |
| Width | 120 mm | |
| Height | 120 mm | |
| Dimensions (L × W × H) | 120 × 120 × 120 mm | |
| Weight | 6.2 kg | |
| Enclosure reference | EPH 3 or EPN 2 | |
| Product range | ETE Stock Control Transformers | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV500P1S1 is a 500 VA single-phase multi-voltage control transformer used to provide selectable nominal 55 V AC or 110 V AC control power for compatible industrial machinery, electrical panels and automation equipment.
The transformer has a rated apparent power of 500 VA (0.5 kVA). This is the overall transformer rating and must not be interpreted as 500 VA independently available from each secondary tap.
The transformer features 10/0/220/240 V primary terminals, including nominal 220 V and 240 V AC primary voltage selections. The correct connection arrangement must follow ETE instructions.
The 10 V primary adjustment tap provides an additional connection facility within the primary winding arrangement. Its correct use and wiring configuration must be confirmed with ETE before installation.
The transformer has 0/55/110 V secondary terminals and supports selectable nominal 55 V AC or 110 V AC output using the appropriate secondary tap.
Yes. The MV500P1S1 includes a 55 V secondary tap for compatible industrial control equipment requiring a nominal 55 V AC supply. The connected load must remain within the transformer's rated capacity.
Yes. The MV500P1S1 includes a 110 V secondary tap for compatible industrial control equipment requiring a nominal 110 V AC supply. The connected load must remain within the transformer's rated capacity.
The transformer has a tapped secondary winding, but simultaneous loading of both taps should not be assumed without confirmation from ETE. Any approved loading arrangement must remain within the overall 500 VA rating and the manufacturer's winding limits.
At the rated 500 VA capacity and a nominal 55 V AC output, the calculated current is approximately 9.09 A. This is a calculated value rather than a separately verified manufacturer current rating.
At the rated 500 VA capacity and a nominal 110 V AC output, the calculated current is approximately 4.55 A. This is a calculated value rather than a separately verified manufacturer current rating.
The MV500P1S1 has a specified 8% voltage regulation. Transformer voltage regulation describes the change in secondary voltage between defined load conditions, so connected equipment should have suitable operating voltage tolerance.
The transformer uses Class E insulation, providing a defined thermal insulation classification for its winding insulation system.
The transformer measures 120 × 120 × 120 mm (L × W × H) and weighs 6.2 kg. These details assist with electrical panel layout, mechanical support and installation planning.
The associated enclosure references are EPH 3 or EPN 2. The appropriate enclosure arrangement and its suitability for the installation should be confirmed before selection.
Before installation, confirm the correct 10/0/220/240 V primary connections and the use of the 10 V adjustment tap with ETE. Select the appropriate 55 V or 110 V secondary connection, check the connected load against the 500 VA rating, and provide suitable circuit protection, conductor sizing, mounting, ventilation and electrical clearances.
ETE MV multi-voltage control transformers provide a practical solution for industrial electrical applications requiring flexible primary connections and selectable AC control voltages. With 10/0/220/240 V primary terminals, 55 V or 110 V secondary output options, a 500 VA rating, Class E insulation and compact dimensions, the MV500P1S1 offers electrical panel builders, machinery manufacturers and automation engineers a versatile transformer option for industrial control power.